A Series

®

Lighting Controller Modbus Register Map

Fixed-Value (Device Object) Registers

6

Reg10041 to Reg10046 – Product Id –
0x444C432B473136343245 – “DLC+G1642E”
All unused bytes are filled with zeros.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

04

Function

04

Register Address Hi

27

Byte Count

0E

Register Address Lo

37

Reg10040 Hi

00

Quantity of Input Reg. Hi

00

Reg10040 Lo

0A

Quantity of Input Reg. Lo

07

Reg10041 Hi

44

Packet CRC Hi

Reg10041 Lo

4C

Packet CRC Lo

Reg10042 Hi

43

Reg10042 Lo

2B

Reg10043 Hi

47

Reg10043 Lo

31

Reg10044 Hi

36

Reg10044 Lo

34

Reg10045 Hi

32

Reg10045 Lo

45

Reg10046 Hi

00

Reg10046 Lo

00

Packet CRC Hi

Packet CRC Lo

Table 6. Sample packet for device product ID.

Latitude and Longitude

Table 7 shows the result of a request for device latitude
and longitude: Reg10022–Reg10025 (Function 04, DEV1
in map).
The response is as follows:
Reg10022 to Reg10023 – Latitude – 0x4226CCCD – 41.7
degrees North
Reg10024 to Reg10025 – Longitude – 0x428FCCCD – 71.9
degrees West (–71.9)

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

04

Function

04

Register Address Hi

27

Byte Count

08

Register Address Lo

25

Reg10022 Hi

42

Quantity of Input Reg. Hi

00

Reg10022 Lo

26

Quantity of Input Reg. Lo

04

Reg10023 Hi

CC

Packet CRC Hi

Reg10023 Lo

CD

Packet CRC Lo

Reg10024 Hi

C2

Reg10024 Lo

8F

Reg10025 Hi

CC

Reg10025 Lo

CD

Packet CRC Hi

Packet CRC Lo

Table 7. Sample packet for device latitude and longitude.

Last Reset

Table 8 shows the result of a request for device last reset
time and date and reset count: Reg10029–Reg10033
(Function 04, DEV1 in map).

The response is as follows:
Reg10029 to Reg10030 – Last Reset Time: 0x0E080400 –
14:08:04.00
Reg10031 to Reg10032 – Last Reset Date: 0x 04040368 –
Thursday Mar 4, 2004
Reg10033 – Reset Count – 0x0005 – 5

Our base year is 1900 ie. 0x68 (104)

Year = 1900+104=2004

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

04

Function

04

Register Address Hi

27

Byte Count

0A

Register Address Lo

2C

Reg10029 Hi

0E

Quantity of Input Reg. Hi

00

Reg10029 Lo

08

Quantity of Input Reg. Lo

05

Reg10030 Hi

04

Packet CRC Hi

Reg10030 Lo

00

Packet CRC Lo

Reg10031 Hi

04

Reg10031 Lo

04

Reg10032 Hi

03

Reg10032 Lo

68

Reg10033 Hi

00

Reg10033 Lo

05

Packet CRC Hi

Packet CRC Lo

Table 8. Sample packet for device last reset date, time, and count.