Objects supported by the lighting controller, A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 9

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Introduction

3






Function

Code

Command

Purpose

Register Group

01

Read Coil Status

Read results or status of coils

Command coils, binary outputs

02

Read Input Status

Read physical binary inputs

Input status

03

Read Holding Registers

Reading the setpoint registers

Fixed value registers, setpoint
registers

04

Read Input Registers

Reading actual value registers

Schedule event registers and
feedback inputs

05

Force Single Coil

Setting the signal coil or
executing single command

Command coils, binary outputs

06

Preset Single Register

Write data into register

Setpoint registers

15

Force Multiple Coils

Write data to multiple outputs

Binary outputs

16

Write Multiple Registers Write data into multiple register Setpoint registers, etc.

Table 1. Function codes supported by the Lighting Controller.

Function Name

Purpose

2

Invalid register

The Register address is not recognized or defined by the Lighting
Controller.

3

Invalid data value

Data out of range

83h

Partial register read

Partial property read

84h

Partial register write

Partial property write

85h

Write protect violation

Write to a read only property.

86h

Single write entry violation

Multiple entries on single write packet, which is restricted to one entry
modification due to array shuffling. NOTE: Only for LG lighting
outputs and common group properties.

89h

Invalid property read/write

Fail to read/write a property due to restriction.

Table 2. Exception response codes.


Objects Supported by the
Lighting Controller

The Lighting Controller supports the object types listed in
Error! Reference source not found..

Register Types

All registers are defined as read only except coil and
setpoint registers. Fixed-value register addresses start at
0201 and are read by function code 04. Actual-value


register addresses start at 1000 and are read by function
code 03. Event register addresses start at 20001 and are
read by function code 04.
All registers consist of 16-bit integers, with values less than
256 stored in the lower byte. Inputs, outputs, and binary
values use Modbus coils and input bit order.
The Modbus device is mapped to a BACnet database.

The Modbus object ID for BACnet object type is given in
Table4.