A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual
Page 18
A Series
®
Lighting Controller Modbus Register Map
Physical Input Registers-Multistate Inputs (MI)
12
The format of the Multi-state Input’s
associated MIC reference is shown in table
18. Changing the MIC reference changes
how the Multi-state Input’s value is
interpreted. (Ex for MI-301).
Offset
Modbus Reg
DB Size
Property
Format
Range
Type
0
40201
WORD
Value From
Int
0 – 2
0 = MIC Standard
1 = reserved
2 = MIC Stepping
RW
Configuration Ref.
1
40202
WORD
Object Type
Word
183 [MIC]
RW
2
40203
WORD
Object Instance
Word
1 = MIC1 (GE Switch)
2 = MIC2 (On/Off)
RW
3 registers per MI
Table 18. Format of Multi-state Input associated MIC reference
Note: Configuration Reference registers (i.e. 40202 and 40203) must be written in a single write using
Function 16.