Lighting Controller Modbus Register Map

Physical Input Registers-Multistate Inputs (MI)

12

The format of the Multi-state Input’s
associated MIC reference is shown in table
18. Changing the MIC reference changes

how the Multi-state Input’s value is
interpreted. (Ex for MI-301).







Offset

Modbus Reg

DB Size

Property

Format

Range

Type

0

40201

WORD

Value From

Int

0 – 2

0 = MIC Standard

1 = reserved

2 = MIC Stepping

RW

Configuration Ref.

1

40202

WORD

Object Type

Word

183 [MIC]

RW

2

40203

WORD

Object Instance

Word

1 = MIC1 (GE Switch)

2 = MIC2 (On/Off)

RW

3 registers per MI

Table 18. Format of Multi-state Input associated MIC reference



Note: Configuration Reference registers (i.e. 40202 and 40203) must be written in a single write using
Function 16.