A Series

®

Lighting Controller Modbus Register Map

Lighting Group Objects

29

Sample Packets

The following are examples of requests to specific setup
registers.

Read for LG1 OutOfService Value

Table 49 is an example of read for LG1 OutOfService,
Value and Current Priority for Reg4001–Reg4003
(Function 3, LG 1in map).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

03

Function

03

Register Address Hi

0F

Byte Count

06

Register Address Lo

A0

Register Value Hi (4001)

00

No. of Registers Hi

00

Register Value Lo (4001)

00

No. of Registers Lo

03

Register Value Hi (4002)

00

Packet CRC Hi

Register Value Lo (4002)

02

Packet CRC Lo

Register Value Hi (4003)

00

Register Value Lo (4003)

06

Packet CRC Hi

Packet CRC Lo

Table 49. Sample packets for read for Reg4001–Reg4003.

Response is as follows:

Reg4001 (OutOfService) 0x0000 – FALSE,
Reg4002 (Value) 0x0002 – Override
Reg4003 (Current Priority) 0x0006 – Priority 6

Read LG Photocell Reference

Table 50 is an example of read LG Photocell Reference
(Object Type, Object Instance and Panel Number) for
Reg. 4009–Reg4011 (Function 3, LG1 in map).
The response is Photocell Reference Object Type 1
(AI), Object Instance 2, Panel Number 100.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

03

Function

03

Register Address Hi

0F

Byte Count

06

Register Address Lo

A8

Register Value Hi (4009)

00

No. of Registers Hi

00

Register Value Lo (4009)

64

No. of Registers Lo

03

Register Value Hi (4010)

00

Packet CRC Hi

Register Value Lo (4010)

00

Packet CRC Lo

Register Value Hi (4011)

00

Register Value Lo (4011)

02

Packet CRC Hi

Packet CRC Lo

Table 50. Sample packets for read LG photocell reference for Reg4009–4011.

Read Lighting Output Array

Table 51 is an example of read Lighting Output Array
Entry 2 Reg4035–Reg4042 (Function 3, LG1 in map).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

03

Function

03

Register Address Hi

0F

Byte Count

10

Register Address Lo

C2

Register Value Hi (4035)

00

No. of Registers Hi

00

Register Value Lo (4035)

64

No. of Registers Lo

08

Register Value Hi (4036)

00

Packet CRC Hi

Register Value Lo (4036)

04

Packet CRC Lo

Register Value Hi (4037)

00

Register Value Lo (4037)

02

Register Value Hi (4038)

00

Register Value Lo (4038)

64

Register Value Hi (4039)

00

Register Value Lo (4039)

0D

Register Value Hi (4040)

00

Register Value Lo (4040)

66

Register Value Hi (4041)

00

Register Value Lo (4041)

00

Register Value Hi (4042)

00

Register Value Lo (4042)

02

Packet CRC Hi

Packet CRC Lo

Table 51. Sample packets for read for lighting output array.

The response to reading Array Index 2 of Lighting
Output, which consists of Output Reference and Switch
Reference, is as follows:

Reg4035–Reg3037 Output Reference object:

0x006400040002 - 100.BO2

Reg4038–Reg4040 Switch Reference object:

0x0063000E0065 - 100.MI101

Reg4041 Reference Value: 00000
Reg4042 Switch Value: 0002

Single Write OFF to Lighting Group 1

Table 52 is an example of a single write OFF (0x0000)
to LG1 Value Reg4002 (Function 6, LG 1in map). Note
that OutOfService is automatically set to TRUE with
this write.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

06 Function

06

Register Address Hi

0B Register Address Hi

0B

Register Address Lo

B9 Register Address Lo

B9

Register Value Hi

00 Register Value Hi

00

Register Value Lo

00 Register Value Lo

00

Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 52. Sample packets for single write OFF to LG 1.