A Series

®

Lighting Controller Modbus Register Map

Physical Input Registers-Multistate Inputs (MI)

10

Read MI Reg15 to Reg18

Table 13 shows the result of a request to
read MI Reg15 to Reg18 (Function 4,
MI115–MI116 and MI201–MI202 in map).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

04 Function

04

Register Address
Hi

00 Byte Count

08

Register Address
Lo

0E Input 115 Hi

00

Quantity of Input
Reg. Hi

00 Input 115 Lo

01

Quantity of Input
Reg. Lo

04 Input 116 Hi

00

Packet CRC Hi

Input 116 Lo

02

Packet CRC Lo

Input 201 Hi

00

Input 201 Lo

01

Input 202 Hi

00

Input 202 Lo

03

Packet CRC Hi

Packet CRC Lo

Table 13. Sample packet for read of MI Reg15 to Reg18.

Write to MI Reg15

Table 14 shows the result of a write to MI
Reg15 (Function 5 Single Write, MI115 in
map). Note that the packet shows an error,
since MI values are read only.

Request

Response

Field Name

He

x

Field Name

Hex

Device Address

01 Device

Address

01

Function

05 Error Code

85

Register Address Hi

00 Exception

Code

85

Register Address Lo

0E Packet CRC

Hi

Quantity of Input Reg.
Hi

00 Packet CRC

Lo

Quantity of Input Reg.
Lo

01

Packet CRC Hi

Packet CRC Lo

Table 14. Sample packet for write of MI Reg15.