5

Fixed-Value Registers

Fixed-value register addresses start at 10001 and are read
by Function Code 04. They are mapped to Device
properties. These properties are assigned constant values
at the time of manufacture and may be stored in the
onboard EEPROM rather than in the database.
The fixed-value (device object property) registers are
listed in Table 5.

All strings have an embedded length. The first two
registers of the string contain the length of the string; e.g.,
Product ID Reg10040 Hi contains the most-significant
byte and Reg10040 Lo contains the least-significant byte of
the string length. The first character starts at Reg10041
Hi, the second character in Reg10041 Lo, the third
character in Reg10042 Hi, and so forth.

Offset Modbus # reg

Property

Format

Range

Type

0

10001–10007

Firmware Version

ASCII

Int (ASCII string)

12 chars max + 2 bytes string size

R

7

10008–10014

Hardware Revision

ASCII

Int (ASCII string)

12 chars max + 2 bytes string size

R

14

10015–10021

Application software

version

ASCII

Int (ASCII string)

12 chars max

R

21

10022–10023

Latitude

1

Real

±90.0

R

23

10024–10025

Longitude

2

Real

±180.0

R

25

10026

UTC Enable

Int

0 /1

R

26

10027

UTC Offset

Int

±32767

R

27

10028

DST Enable

Int

0/1

R

Last Reset Time/Date

28

10029

Hours/Minutes

Word

R

29

10030

Seconds/Hundreths sec

Word

R

30

10031

DayOfWeek/Day

Word

R

31

10032

Month/Year

Word

R

32

10033

Reset Count

Word

1–65536

R

33

10034

Device Address

(Mac address)

Word

1–99

R

34

10035

Device Control

Word

See Reg 50035

NA

Current Time/Date

35

10036

Hours/Minutes

Word

R

36

10037

Seconds/Hundredths Sec

Word

R

37

10038

DayofWeek/Day

Word

R

38

10039

Month/Year

Word

R

39

10040–10046

Product ID

ASCII

INT (ASCII string)

12 chars max + 2 bytes string size

R

1 Latitude: positive value is north, negative value is south.
2 Longitude: positive value is east, negative value is west.

Table 5. Types of fixed-value registers.

Date and time values are represented as follows:

• Week of day: 1–7, 255 (wildcard)

• Day: 1–31, 255 (wildcard)

• Month: 1–12, 255 (wildcard)
• Year: 0–255
• Hour: 0–23, 255 (wildcard)
• Minutes: 0–59, 255 (wildcard)
• Seconds: 0–59, 255 (wildcard)
• Hundredths of seconds: 0–99, 255 (wildcard)

Sample Packets

The following are examples of packets generated by
requests for specific properties.

Device Product ID

Table 6 shows the result of a request for device product ID:
Reg10040 to Reg10046 (Function 04, DEV1 in map).
The response is as follows:
Reg10040 – Product Id Length – 0x000A – 10 characters