A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 21

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Physical Input Registers-Analog Input (AI)

15

Reg1001 (OutOfService) 0x0000 – FALSE,

Reg1002 – 1003 (Value) 0x41A00000 – 20.0

Reg1004 – 1005 (Calibration) 0x40A00000 – 5.0,

Reg1006 (Commission) 0x0001 – TRUE,

Reg1007 (Reliability) 0x0000 – Normal,

Reg1008 – 1009 (Configuration Reference) 0x000B0001 – AIC1

Table 23 shows the result of read request for AI601 object (Registers 1101-1109)

Read entire AI601 object – Registers 1101-1109



Request

Response

Field Name

(Hex)

Field Name

(Hex)

Device Address

01

Device Address

01

Function

03

Function

03

Starting Address Hi

04

Byte Count

0E

Starting Address Lo

4C

Reg. Value Hi (1101)

00

Quantity of Input Reg. Hi

00

Reg. Value Lo (1101)

00

Quantity of Input Reg. Lo

07

Reg. Value Hi (1102)

42

Packet CRC Hi

Reg. Value Lo (1102)

C8

Packet CRC Lo

Reg. Value Hi (1103)

00

Reg. Value Lo (1103)

00

Reg. Value Hi (1104)

3F

Reg. Value Lo (1104)

80

Reg. Value Hi (1105)

00

Reg. Value Lo (1105)

00

Reg. Value Hi (1106)

00

Reg. Value Lo (1106)

01

Reg. Value Hi (1107)

00

Reg. Value Lo (1107)

00

Reg. Value Hi (1108)

00

Reg. Value Lo (1108)

0B

Reg. Value Hi (1109)

00

Reg. Value Lo (1109)

01

Packet CRC Hi

Packet CRC Lo

Table 23.Sample packet for read of AI 601 register

NOTE: Response for AI601 properties

Reg1001 (OutOfService) 0x0000 – FALSE

Reg1002 – 1003 (Value) 0x42C80000 – 100.0

Reg1004 – 1005 (Calibration) 0x3F800000 – 1.0

Reg1006 (Commission) 0x0001 – TRUE

Reg1007 (Reliability) 0x0000 – Normal

Reg1008 – 1009 (Configuration Reference) 0x00B00001 – AIC1