Lighting Controller Modbus Register Map

Schedule Objects

35

Multiple Write Changing a Day Schedule

Table 65 is an example of a multiple write to change the
Day1 schedule (Function 16, SCH1in map).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

03 Function

10

Register Address Hi

4E Register Address Hi

4E

Register Address Lo

23 Register Address Lo 23

No. of Registers Hi

00 No. of Registers Hi

00

No. of Registers Lo

0C No. of Registers Lo

0C

Register Value Hi (20004)

06

Register Value Lo (20004)

00

Register Value Hi (20005)

00

Register Value Lo (20005)

01

Register Value Hi (20006)

07

Register Value Lo (20006)

00

Register Value Hi (20007)

00

Register Value Lo (20007)

00

Register Value Hi (20008)

08

Register Value Lo (20008)

00

Register Value Hi (20009)

00

Register Value Lo (20009)

01

Register Value Hi (20010)

12

Register Value Lo (20010)

00

Register Value Hi (20011)

00

Register Value Lo (20011)

00

Register Value Hi (20012)

14

Register Value Lo (20012)

00

Register Value Hi (20013)

00

Register Value Lo (20013)

01

Register Value Hi (20014)

17

Register Value Lo (20014)

2D

Register Value Hi (20015)

00

Register Value Lo (20015)

00

Packet CRC Hi

Packet CRC Lo

Table 65. Sample packets for multiple write changing a day schedule.







Single Write to Remove an Entry

Table 66 is an example of a single write to remove entry 4
(Reg.20008–Reg.20009). Write 0xFFFF to the first entry to
remove (Reg.20008).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

06 Function

06

Register Address Hi

4E Register Address Hi

4E

Register Address Lo

27 Register Address Lo

27

Register Value Hi (20008) FF Register Value Hi (20008) FF
Register Value Lo

(20008)

FF

Register Value Lo
(20008)

FF

Register Value Hi (20009) FF Register Value Hi (20009) FF
Register Value Lo

(20009)

FF

Register Value Lo
(20009)

FF

Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 66. Sample packets for a single write to remove an entry.