Lighting Controller Modbus Register Map

Physical Input Registers-Analog Input (AI)

14


Offset Modbus Regs DB size

Property

Format

Range

Type

0

1001

Bit

OutOfService

Int

0 – 1

RW

1

1002

FLOAT Hi Value *

0 – 65535

RW

2

1003

FLOAT Lo

0 – 65535

RW

3

1004

FLOAT Hi Calibration

0 – 65535

RW

4

1005

FLOAT Lo

0 – 65535

RW

5

1006

Bit

Commissioned

Int

0 – 1

RW

6

1007

WORD

Reliability

Int

Enum

R

Configuration Ref.

7

1008

WORD

Object Type

176 [AIC]

RW

8

1009

WORD

Object Instance

1 – 65535

1 = Photodiode Linear
2 = Photoconductive
3 = Photodiode Linear (Inverse)
4 = Photoconductive (Inverse)

RW

9 registers per AI

Table 21. Property of AI1 object

Note:

AIC reference registers 1008 and 1009 must be written in a single write using Function
16.

Analog Input Configuration (AIC) object type in Hexadecimal is <00B0>

Sample packets

Table 22 indicates the result of read request for AI1 object

Request

Response

Field Name

(Hex)

Field Name

(Hex)

Device Address

01

Device Address

01

Function

03

Function

03

Starting Address Hi

03

Byte Count

0E

Starting Address Lo

E8

Reg. Value Hi (1001)

00

Quantity of Input Reg. Hi

00

Reg. Value Lo (1001)

00

Quantity of Input Reg. Lo

07

Reg. Value Hi (1002)

41

Packet CRC Hi

Reg. Value Lo (1002)

A0

Packet CRC Lo

Reg. Value Hi (1003)

00

Reg. Value Lo (1003)

00

Reg. Value Hi (1004)

40

Reg. Value Lo (1004)

A0

Reg. Value Hi (1005)

00

Reg. Value Lo (1005)

00

Reg. Value Hi (1006)

00

Reg. Value Lo (1006)

01

Reg. Value Hi (1007)

00

Reg. Value Lo (1007)

00

Reg. Value Hi (1008)

00

Reg. Value Low(1008)

0B

Reg. Value Hi (1009)

00

Reg. Value Low(1009)

01

Packet CRC Hi

Packet CRC Lo

Table 22 Sample packet for read of AI1 register

NOTE: Response for AI1 properties