A Series

®

Lighting Controller Modbus Register Map

Physical Output Registers-Binary Outputs (BO)

20

2559 – 2576

BO32

RW

2577 – 2594

BO33

RW

2595 – 2612

BO34

RW

2613 – 2630

BO35

RW

2631 – 2648

BO36

RW

2649 – 2666

BO37

RW

2667 – 2684

BO38

RW

2685 – 2702

BO39

RW

2703 – 2720

BO40

RW

2721 – 2738

BO41

RW

2739 – 2756

BO42

RW

2757 – 2774

BO43

RW

2775 – 2792

BO44

RW

2793 – 2810

BO45

RW

2811 – 2828

BO46

RW

2829 – 2846

BO47

RW

2847 – 2864

BO48

RW

2865 – 2882

BO49

RW

2883 – 2900

BO50

RW

2901 – 2918

BO51

RW

2919 – 2936

BO52

RW

2937 – 2954

BO53

RW

2955 – 2972

BO54

RW

2973 – 2990

BO55

RW

2991 – 3008

BO56

RW

3009 – 3026

BO57

RW

3027 – 3044

BO58

RW

3045 – 3062

BO59

RW

3063 – 3080

BO60

RW

3081 – 3098

BO61

RW

3099 – 3116

BO62

RW

3117 – 3134

BO63

RW

3135 – 3152

BO64

RW

3153 – 3170

BO65

RW

3171 – 3188

BO66

RW

Table 33. Binary Output (BO) Registers

Offset Modbus regs DB size

Property

Format

Range

Type

0

2001

Bit

OutOfService

Int

0–1

RW

1

2002

Byte

Value

Int

0–1

RW

2

2003

Bit

Commissioned

Int

0–1

RW

3

2004

Word

Reliability

Int

Enum

R

4

2005–2006

Dword

MinimumOffTime

Word

0–65536

RW

6

2007–2008

Dword

MinimumOnTime

Word

0–65536

RW

8

2009

Byte

DefaultValue

Word

0–65536

RW

9

2010–2011

Dword

StartDelayTime

Word

0–65536

RW

11

2012

Byte

FbackValue

Word

0–65536

RW

12

2013

Byte

FlickWarnTime

Word

0–65536

RW

13

2014

Word

FlickWarnPAEnable

Int

On/Off

RW

14

2015

Word

OverrideTime

Word

0–65536

RW

Table 34. Address space of binary output registers.


Binary Output (BO) Properties:

Each Binary Output (BO) object exposes the following
object properties (Table 34).

Sample Packets

Following are examples of function requests to binary
output registers.







Read All BO1 Properties

Table.35 is an example of a read of all BO1 properties:
OutOfService, Value, Commissioned, Reliability and
MinimumOffTime Reg2001–Reg2006 (Function 3, BO1in
map).