Lighting group objects, Lighting group registers (outofservice), Lighting group setup registers – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 32: A series, Lighting group output registers (coils), Sample packets

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Lighting Group Objects

26

Lighting Group Objects

Individual binary outputs can be grouped together to
represent the logical layout of a building installation.
Sixteen lighting groups (LG) are available and each one
can contain a group of 33 outputs.

Lighting Group Output Registers (Coils)

Actual value registers start at 301. The Lighting Group
and OutOfService property can be commanded by
Function Code 05 and 15 and read by Function Code 1
and are mapped to Lighting Group Instances 1–16. The
value in the register represents the Lighting Group’s
PresentValue.The Lighting Group output registers are
listed inTable 43.

Reg.

Contents

Type

Format Instance

301

LG01 Value

RW

On/Off

01

302

LG02 Value

RW

On/Off

02

303

LG03 Value

RW

On/Off

03

304

LG04 Value

RW

On/Off

04

305

LG05 Value

RW

On/Off

05

306

LG06 Value

RW

On/Off

06

307

LG07 Value

RW

On/Off

07

308

LG08 Value

RW

On/Off

08

309

LG09 Value

RW

On/Off

09

310

LG10 Value

RW

On/Off

10

311

LG11 Value

RW

On/Off

11

312

LG12 Value

RW

On/Off

12

313

LG13 Value

RW

On/Off

13

314

LG14 Value

RW

On/Off

14

315

LG15 Value

RW

On/Off

15

316

LG16 Value

RW

On/Off

16

Table 43. Lighting Group output registers.

Sample Packets

Table44 is an example of a request for LG Value Reg302
to Reg305 (Function Code 1, LG2 – LG5 in map).
Note that the status of outputs 5–2 is hex 0B or binary
0000 1011, where LG302 is the LSB and LG305 is the
fourth bit from the left. Unused bits are padded as zero.

Request

Response

Field Name

Hex

Field Name

Hex

Device Address

01

Device Address

01

Function

01

Function

01

Register Address Hi

01

Byte Count

01

Register Address Lo

2D

Output Status 5–2

0B

Quantity of LG Hi

00

Packet CRC Hi

Quantity of LG Lo

04

Packet CRC Lo

Packet CRC Hi

Packet CRC Lo

Table 44. Sample packets for LG Value Reg302 to Reg305.

Lighting Group Registers
(OutOfService)

The Lighting Group OutOfService registers are listed in
Table45.

Reg.

Contents

Type Format Instance

401

LG01 OutOfService

RW

On/Off

01

402

LG02 OutOfService

RW

On/Off

02

403

LG03 OutOfService

RW

On/Off

03

404

LG04 OutOfService

RW

On/Off

04

405

LG05 OutOfService

RW

On/Off

05

406

LG06 OutOfService

RW

On/Off

06

407

LG07 OutOfService

RW

On/Off

07

408

LG08 OutOfService

RW

On/Off

08

409

LG09 OutOfService

RW

On/Off

09

410

LG10 OutOfService

RW

On/Off

10

411

LG11 OutOfService

RW

On/Off

11

412

LG12 OutOfService

RW

On/Off

12

413

LG13 OutOfService

RW

On/Off

13

414

LG14 OutOfService

RW

On/Off

14

415

LG15 OutOfService

RW

On/Off

15

416

LG16 OutOfService

RW

On/Off

16

Table 45. Lighting Group OutOfService registers.

Sample Packets

Table 46 is an example of a request for LG OutOfService
status instance 401–416 (Function Code 1, LG1–16 in
map).
Note that the LG OutOfService Status of 408–401 is shown
as hex AB or binary 1010 1011, where LG 401 is the LSB
and LG408 is the MSB.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

01 Function

01

Register Address Hi

01 Byte Count

02

Register Address Lo 90 OutOfService Reg408–401

AB

Quantity of LG Hi

00 OutOfService Reg416–409

AA

Quantity of LG Lo

10 Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 46. Sample packets for LG out of Service instance 401–416.

Lighting Group Setup Registers

The Lighting Group setup parameters are assigned a
block of holding registers starting at 4001 as indicated in
table 47. Lighting Group properties can be commanded

Advertising