A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 27

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Physical Output Registers-Binary Outputs (BO)

21

Request

Response

Field Name

Hex

Device Address

01 Field Name

Hex

Function

03 Device Address

01

Register Address Hi

00 Function

03

Register Address Lo

00 Byte Count

0C

Registers Hi

00 Register Value Hi (2001)

00

Registers Lo

06 Register Value Lo (2001)

00

Packet CRC Hi

Register Value Hi (2002)

00

Packet CRC Lo

Register Value Lo (2002)

01

Register Value Hi (2003)

00

Register Value Lo (2003)

00

Register Value Hi (2004)

00

Register Value Lo (2004)

00

Register Value Hi (2005)

00

Register Value Lo (2005)

00

Register Value Hi (2006)

00

Register Value Lo (2006)

3C

Packet CRC Hi

Table 35. Sample packets for read of all BO1 properties.

The response is as follows:

Reg2001 (OutOfService): 0x0000, FALSE,
Reg2002 (Value): 0x0001, ON
Reg2003 (Commissioned): 0x000, FALSE
Reg2004 (Reliability): 0x0000, Normal,
Reg2005 (MinimumOffTime): 0x0003C, 60sec

Single Write to BO1 Override Time

Table.36 is an example of a single write of 5 minutes
(0x0005) to BO1 Override Time Reg.2015 (Function 6,
BO1 in map).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

06 Function

06

Register Address Hi

07 Register Address Hi

07

Register Address Lo

DE Register Address Lo

DE

Registers Hi

00 Registers Hi

00

Registers Lo

05 Registers Lo

05

Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 36. Sample packets for single write to BO1 overwrite time.

Multiple Write to Binary Output

Table.37 is an example of a multiple write to BO
OutOfService and Value 1–3 (Function 16, BO 1in map).
This example writes OutOfService to TRUE and Value to
0x0000 (OFF).

Request

Response

Field Name

Hex

Field Name

Hex

Device Address

01

Device Address

01

Function

10

Function

10

Register Address Hi

07

Register Address Hi

00

Register Address Lo

D0

Register Address Lo

00

Registers Hi

00

Registers Hi

00

Registers Lo

02

Registers Lo

02

Register Value 1 Hi

00

Packet CRC Hi

Register Value 1 Lo

01

Packet CRC Lo

Register Value 2 Hi

00

Register Value 2 Lo

00

Packet CRC Hi

Packet CRC Lo

Table 37. Sample packets for multiple write to binary output.

Advertising