Physical output registers (outofservice), A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 24

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Physical Output Registers-Binary Outputs (BO)

18

Read Coil Status of BO Reg2 to Reg19

Table 28 shows the result of a request to read the coil
status of BO Reg2–Reg19 (Function 1, BO2–19 in map).
Note that the status of outputs 19–18 is shown as the byte
value 0x03 or binary 0000 0011 and output 18 is the LSB.
The six remaining high-order bits are zero filled.

Request

Response

Field Name

Hex

Field Name

Hex

Device Address

01

Device Address

01

Function

01

Function

01

Register Address Hi

00

Byte Count

03

Register Address Lo

01

Output Status 9–2

AC

Quantity of Outputs Hi

00

Output Status 17–10

0A

Quantity of Outputs Lo

12

Output Status 19–18

03

Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 28. Sample packet for coil status of BO Reg2 to Reg19.

Read Coil Status of BO Reg62 to Reg66

Table 29 shows the result of a request to read the coil
status of BO Reg62–Reg66 (Function 1, BO62–66). Note
that the status of outputs 66–62 is shown as the byte value
0x37 or binary 0001 0111 and output 62 is the LSB. The
remaining two high-order bits are zero filled.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

01

Function

01

Register Address Hi

00

Byte Count

03

Register Address Lo

3D Output Status 66–62

17

Quantity of Outputs Hi

00

Packet CRC Hi

Quantity of Outputs Lo

05

Packet CRC Lo

Packet CRC Hi

Packet CRC Lo

Table 29. Sample packet for coil status of BO Reg62 to Reg 66.

The output values are

Reg62: BO62 Value – ON
Reg63: BO63 Value – ON

Reg64: BO64 Value – ON

Reg65: BO65 Value – OFF
Reg66: BO66 Value – ON

Physical Output Registers
(OutOfService)

Actual value registers start at 201, commanded by
Function Code 01, 05, or 15 and mapped to Binary
Outputs (BO) 1–66. The address space is reserved to 900.
The value in the register represents the Binary Output’s
OutOfService value. A value of 1 corresponds to manual

mode, 0 to auto mode.The physical output registers
(OutOfService) are listed in Table 30.

Reg.

Contents

Type

Format

BO

Instance

201

BO1 OutOfService

RW

ON/OFF

01

202

BO2 OutOfService

RW

ON/OFF

02

203

BO3 OutOfService

RW

ON/OFF

03

204

BO4 OutOfService

RW

ON/OFF

04

205

BO5 OutOfService

RW

ON/OFF

05

206

BO6 OutOfService

RW

ON/OFF

06

207

BO7 OutOfService

RW

ON/OFF

07

208

BO8 OutOfService

RW

ON/OFF

08

209

BO9 OutOfService

RW

ON/OFF

09

210 BO10 OutOfService

RW

ON/OFF

10

211 BO11 OutOfService

RW

ON/OFF

11

212 BO12 OutOfService

RW

ON/OFF

12

213 BO13 OutOfService

RW

ON/OFF

13

214 BO14 OutOfService

RW

ON/OFF

14

215 BO15 OutOfService

RW

ON/OFF

15

216 BO16 OutOfService

RW

ON/OFF

16

217 BO17 OutOfService

RW

ON/OFF

17

218 BO18 OutOfService

RW

ON/OFF

18

219 BO19 OutOfService

RW

ON/OFF

19

220 BO20 OutOfService

RW

ON/OFF

20

221 BO21 OutOfService

RW

ON/OFF

21

222 BO22 OutOfService

RW

ON/OFF

22

223 BO23 OutOfService

RW

ON/OFF

23

224 BO24 OutOfService

RW

ON/OFF

24

225 BO25 OutOfService

RW

ON/OFF

25

226 BO26 OutOfService

RW

ON/OFF

26

227 BO27 OutOfService

RW

ON/OFF

27

228 BO28 OutOfService

RW

ON/OFF

28

229 BO29 OutOfService

RW

ON/OFF

29

230 BO30 OutOfService

RW

ON/OFF

30

231 BO31 OutOfService

RW

ON/OFF

31

232 BO32 OutOfService

RW

ON/OFF

32

233 BO33 OutOfService

RW

ON/OFF

33

234 BO34 OutOfService

RW

ON/OFF

34

235 BO35 OutOfService

RW

ON/OFF

35

236 BO36 OutOfService

RW

ON/OFF

36

237 BO37 OutOfService

RW

ON/OFF

37

238 BO38 OutOfService

RW

ON/OFF

38

239 BO39 OutOfService

RW

ON/OFF

39

240 BO40 OutOfService

RW

ON/OFF

40

241 BO41 OutOfService

RW

ON/OFF

41

242 BO42 OutOfService

RW

ON/OFF

42

243 BO43 OutOfService

RW

ON/OFF

43

244 BO44 OutOfService

RW

ON/OFF

44

245 BO45 OutOfService

RW

ON/OFF

45

246 BO46 OutOfService

RW

ON/OFF

46

247 BO47 OutOfService

RW

ON/OFF

47

248 BO48 OutOfService

RW

ON/OFF

48

249 BO49 OutOfService

RW

ON/OFF

49

250 BO50 OutOfService

RW

ON/OFF

50

251 BO51 OutOfService

RW

ON/OFF

51