A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 34

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Lighting Group Objects

28

22

4023

Astro On Enable

Int

On/Off

RW

23

4024

Astro Off Enable

Int

On/Off

RW

24

4025

BYTE

Astro On Offset

Int

0 – 254

RW

25

4026

LONG

Astro On Calc Hi** Word

0 – 254

R

26

4027

Astro On Calc Lo** Word

0 – 254

R

27

4028

BYTE

Astro Off Offset

Int

0 – 254

RW

28

4029

LONG

Astro Off Calc Hi** Word

0 – 254

R

29

4030

Astro Off Calc Lo** Word

0 – 254

R

30

4031

BYTE

FlickWarnEnable

Word

1-On / 0-Off

RW

31

4032

BYTE

FlickWarnTime

Word

0 – 240 min

RW

32

4033

WORD

FlickWarnPAEnble

Word

0 – 65535

RW

33

4034

WORD

FlickWarnInputEnb Word

0 – 65535

RW

Array of 33
Output Ref/
Switch Ref
pairs

Lighting Outputs

Output Ref

34

4035

Panel Number

Word

1 – 99

RW

35

4036

Object Type

4 – [BO]

303 – [LG]

RW

36

4037

Object Instance

Word

1 – 65535

RW

Switch Ref

37

4038

Panel Number

Word 1 – 99

RW

38

4039

Object Type

3 – [BI]
13 – [MI]

RW

39

4040

Object Instance

Word 0 – 65535

RW

40

4041

Value

Word

RW

41

4042

Switch Value

Word

RW

42

4043 – 4298

32 more entries:
8 registers per entry

RW

298

4299

Common Off Time Int

0 – 1000

RW

Array of 16

Common Groups

299

4300

Panel Number

Word 1 – 99

RW

300

4301

Object Type

Word 303 – [LG]

RW

301

4302

Object Instance

Word 1 – 16

RW

302

4303

Value

Word

RW

303

4304 – 4363

15 remote LG refs:
4 registers per entry

RW

363 registers / LG

Table 48. Lighting Group setup registers.

Advertising