A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 43

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Calendar Objects

37

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

03 Function

03

Register Address Hi

27 Byte Count

0E

Register Address Lo

10 Register Value Hi (10001)

00

No. of Registers Hi

10 Register Value Lo (10001)

00

No. of Registers Lo

07 Register Value Hi (10002)

00

Packet CRC Hi

Register Value Lo (10002)

00

Packet CRC Lo

Register Value Hi (10003)

00

Register Value Lo (10003)

03

Register Value Hi (10004)

05

Register Value Lo (10004) 0D

Register Value Hi (10005)

02

Register Value Lo (10005)

68

Register Value Hi (10006)

01

Register Value Lo (10006)

0F

Register Value Hi (10007)

03

Register Value Lo (10007)

68

Packet CRC Hi

Packet CRC Lo

Table 69. Sample packets for a read of CAL properties – OutOfService.

Read Calendar Properties Date List

Table 70 is an example of a read of CAL properties: read
the first four entries on the date list: Reg10004–Reg10011
(Function 3, CAL 1in map).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

03 Function

03

Register Address Hi

27 Byte Count

10

Register Address Lo 10 Register Value Hi (10004) 05
No. of Registers Hi

00 Register Value Lo (10004) 0D

No. of Registers Lo

08 Register Value Hi (10005) 02

Packet CRC Hi

Register Value Lo (10005) 68

Packet CRC Lo

Register Value Hi (10006) 01

Register Value Lo (10006) 0F

Register Value Hi (10007) 03

Register Value Lo (10007) 68

Register Value Hi (10008) 04

Register Value Lo (10085) 01

Register Value Hi (10009) 04

Register Value Lo (10009) 68

Register Value Hi (10010) FF

Register Value Lo (10010) FF

Register Value Hi (10011) FF

Register Value Lo (10011) FF

Packet CRC Hi

Packet CRC Lo

Table 70. Sample packets for a read of CAL properties – date entries.

The response is as follows:

Reg10004–Reg10005 first entry: 0x050D0268, Friday Feb

13, 2004

Reg10006–Reg10007

second

entry:

0x010F0368,

Monday Mar 15, 2004

Reg10008–Reg10009 third entry: 0x04010468, Thursday

April 1, 2004

Reg10010–Reg10011 fourth entry: 0xFFFFFFFF, empty

Single Write of True to CAL OutOfService

Table 71 is an example of a single write of True to CAL1
OutOfService Reg.10001 (Function 6, CAL 1 in map).
The response is that OutOfService is True after the write.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

06 Function

06

Register Address Hi

27 Register Address Hi

27

Register Address Lo

10 Register Address Lo

10

Register Value Hi

00 Register Value Hi

00

Register Value Lo

01 Register Value Lo

01

Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 71. Sample packets for a single write of True to CAL1 OutOfService.

Single Write to CAL1 Date List Count

Table72 is an example of a single write of 5 to the CAL1
Date List Count Reg.10003 (Function 6, CAL1 in map).
The response is an error code, since the Date List Count is
a read-only property.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

06 Error Code

86

Register Address Hi

27 Exception Code

85

Register Address Lo

12 Packet CRC Hi

Register Value Hi

00 Packet CRC Lo

Register Value Lo

05

Packet CRC Hi

Packet CRC Lo

Table 72. Sample packets for a single write to the Date List Count Register.

Multiple Write to Edit Entry in Date List

Table 73 is an example of a multiple write to edit the
second entry of the Date List (Function 16, CAL1 in map).
This changes the second entry to August 22, 2004:
0x07160868.




Advertising