A Series

®

Lighting Controller Modbus Register Map

Physical Input Registers-Analog Inputs(AI)

13

Analog Input Registers

Lighting controller contains three on-board Analog
Inputs and upto 16 remote Inputs ( 8 per Daylight
Optimisation module . The present value of the Analog
Input objects are mapped as indicated in table 19.

Analog Input (AI) Value- (Registers 101-148)




Register

AI Input

Type

Format

101 – 102

AI1 On-board

R

Float

103 – 104

AI2 On-board

R

Float

105 – 106

AI3 On-board

R

Float

117 – 118

AI-601

R

Float

119 – 120

AI-602

R

Float

121 – 122

AI-603

R

Float

123 – 124

AI-604

R

Float

125 – 126

AI-605

R

Float

127 – 128

AI-606

R

Float

129 – 130

AI-607

R

Float

131 – 132

AI-608

R

Float

133 – 134

AI-701

R

Float

135 – 136

AI-702

R

Float

137 – 138

AI-703

R

Float

139 – 140

AI-704

R

Float

141 – 142

AI-705

R

Float

143 – 144

AI-706

R

Float

145 – 146

AI-707

R

Float

147 – 148

AI-708

R

Float

Table 19. Analog Input Registers

Analog Input (AI) Object (Registers 1001 – 1272)

Table 20 shows different registers associated with each
AI.





Register

AI Input

Type

Conf

Ref

1001 – 1009

AI1 On-board

RW

1010 – 1018

AI2 On-board

RW

1019 – 1027

AI3 On-board

RW

1101 – 1109

AI-601

RW

AIC1

1110 – 1118

AI-602

RW

AIC1

1119 – 1127

AI-603

RW

AIC1

1128 – 1136

AI-604

RW

AIC1

1137 – 1145

AI-605

RW

AIC1

1146 – 1154

AI-606

RW

AIC1

1155 – 1163

AI-607

RW

AIC1

1164 – 1172

AI-608

RW

AIC1

1201 – 1209

AI-701

RW

AIC1

1210 – 1218

AI-702

RW

AIC1

1219 – 1227

AI-703

RW

AIC1

1228 – 1236

AI-704

RW

AIC1

1237 – 1245

AI-705

RW

AIC1

1246 – 1254

AI-706

RW

AIC1

1255 – 1263

AI-707

RW

AIC1

1264 – 1272

AI-708

RW

AIC1

Table 20. Analog Input Property Registers

Analog Input (AI) Properties:


Each AI object exposes the following properties via
Function codes 3/6/16. There are 6 properties
available: Value, Calibration and Configuration Ref
properties take multiple registers and Value &
Reliability can only be written if OutOfService is True
(OutofService means breaker is in manual mode). To
remove a Configuration Ref, write 0 into the
corresponding registers for object type and instance.
Table 21 shows different registers of AI1 object.