A Series

®

Lighting Controller Modbus Register Map

Physical Output Registers-Binary Outputs (BO)

19

Reg.

Contents

Type

Format

BO

Instance

252 BO52 OutOfService

RW

ON/OFF

52

253 BO53 OutOfService

RW

ON/OFF

53

254 BO54 OutOfService

RW

ON/OFF

54

255 BO55 OutOfService

RW

ON/OFF

55

256 BO56 OutOfService

RW

ON/OFF

56

257 BO57 OutOfService

RW

ON/OFF

57

258 BO58 OutOfService

RW

ON/OFF

58

259 BO59 OutOfService

RW

ON/OFF

59

260 BO60 OutOfService

RW

ON/OFF

60

261 BO61 OutOfService

RW

ON/OFF

61

262 BO62 OutOfService

RW

ON/OFF

62

263 BO63 OutOfService

RW

ON/OFF

63

264 BO64 OutOfService

RW

ON/OFF

64

265 BO65 OutOfService

RW

ON/OFF

65

266 BO66 OutOfService

RW

ON/OFF

66

Table 30. List of physical output registers (OutOfService).

Sample Packets

The following are examples of requests to specific groups
of output registers.

Write to Output Reg201

Table 31 shows the result of a write request to output
OutOfService Reg201 (Function 5 Single Write, BO1 in
map).

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

0F

Function

0F

Register Address Hi

DB Register Address Hi

DB

Register Address Lo

00

Register Address Lo

00

Quantity of Outputs Hi

00

Quantity of Outputs Hi

00

Quantity of Outputs Lo

0A Quantity of Outputs Lo

0A

Byte Count

02

Packet CRC Hi

Output Value Hi

CD Packet CRC Lo

Output Value Lo

03

Packet CRC Hi

Packet CRC Lo

Table 31. Sample packet for multiple write to output Reg220–Reg229.

Multiple Write Output Reg220–Reg229

Table 32 shows the result of a multiple write to BO
OutOfService Reg220–229 (Function 15 Multiple Write,
BO 20–29 in map).
Note that the Hi byte 0xCD addresses outputs 27–20, with
the least-significant bit addressing the lowest output 20
and the most-significant bit addressing the highest output
27. The Lo byte 03 addresses outputs 29–28, with the least-
significant bit addressing the lowest output 28. Unused
bits in the last data byte are padded with zeros

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01

Device Address

01

Function

05

Function

05

Register Address Hi

00

Register Address Hi

00

Register Address Lo

C8 Register Address Lo

C8

Output Value Hi

FF

Output Value Hi

FF

Output Value Lo

00

Output Value Lo

00

Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 32. Sample packet for write to output Reg201.


Binary Output (BO) Object – (Registers 2001 – 3260)

Each Binary Output object contains 12 properties that are
exposed to MODBUS. These object properties are
writable via Function Codes 6 & 16 and readable by
Function Code 3. Writes to the BO Value occur at
BACnet Priority Level 5 (Critical Equipment Control).
Table 33 shows list of registers associated with B01-B066.

Register

BO Object

Type

2001 – 2018

BO1

RW

2019 – 2036

BO2

RW

2037 – 2054

BO3

RW

2055 – 2072

BO4

RW

2073 – 2090

BO5

RW

2091 – 2108

BO6

RW

2109 – 2126

BO7

RW

2127 – 2144

BO8

RW

2145 – 2162

BO9

RW

2163 – 2180

BO10

RW

2181 – 2198

BO11

RW

2199 – 2216

BO12

RW

2217 – 2234

BO13

RW

2235 – 2252

BO14

RW

2253 – 2270

BO15

RW

2271 – 2288

BO16

RW

2289 – 2306

BO17

RW

2307 – 2324

BO18

RW

2325 – 2342

BO19

RW

2343 – 2360

BO20

RW

2361 – 2378

BO21

RW

2379 – 2396

BO22

RW

2397 – 2414

BO23

RW

2415 – 2432

BO24

RW

2433 – 2450

BO25

RW

2451 – 2468

BO26

RW

2469 – 2486

BO27

RW

2487 – 2504

BO28

RW

2505 – 2522

BO29

RW

2523 – 2540

BO30

RW

2541 – 2558

BO31

RW