Schedule, Schedule value registers, Schedule outofservice registers – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 37: A series, Sample packets

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Schedule Objects

31

Schedule

The Controller contains 16 schedule objects that is
written by the Modbus Master. The Schedule Event
value and OutOfService property can be commanded
by Function Codes 05 and 15 and read by Function
Code 1.

Schedule Value Registers

The Schedule value registers are listed in Table 56.

Reg.

Contents

Type

Format Instance

501

SCH01 Value

RW

On/Off

01

502

SCH02 Value

RW

On/Off

02

503

SCH03 Value

RW

On/Off

03

504

SCH04 Value

RW

On/Off

04

505

SCH05 Value

RW

On/Off

05

506

SCH06 Value

RW

On/Off

06

507

SCH07 Value

RW

On/Off

07

508

SCH08 Value

RW

On/Off

08

509

SCH09 Value

RW

On/Off

09

510

SCH10 Value

RW

On/Off

10

511

SCH11 Value

RW

On/Off

11

512

SCH12 Value

RW

On/Off

12

513

SCH13 Value

RW

On/Off

13

514

SCH14 Value

RW

On/Off

14

515

SCH15 Value

RW

On/Off

15

516

SCH16 Value

RW

On/Off

16

Table 56. Schedule value registers.

Sample Packets

Table 57 is an example of a request for SCH Value
Reg501–Reg505 (Function 1, SCH1–5 in map). Note
that SCH Value Status Reg505–501 (SCH05–SCH01) is
shown as hex value 1F or binary 0001 1111, while
Reg501 is the LSB and Reg505 is the fifth bit from the
left.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

01 Function

01

Register Address Hi

01 Byte Count

01

Register Address Lo

F4 SCH OutOfService 505–501

1F

Quantity of SCH Hi

00 Packet CRC Hi

Quantity of SCH Lo

05 Packet CRC Lo

Packet CRC Hi

Packet CRC Lo

Table 57. Sample packets for request for SCH Value.

Schedule OutOfService
Registers

The Schedule OutOfService registers are listed in Table
58.

Reg.

Contents

Type Format Instance

601 SCH01 OutOfService RW On/Off

01

602 SCH02 OutOfService RW On/Off

02

603 SCH03 OutOfService RW On/Off

03

604 SCH04 OutOfService RW On/Off

04

605 SCH05 OutOfService RW On/Off

05

606 SCH06 OutOfService RW On/Off

06

607 SCH07 OutOfService RW On/Off

07

608 SCH08 OutOfService RW On/Off

08

609 SCH09 OutOfService RW On/Off

09

610 SCH10 OutOfService RW On/Off

10

611 SCH11 OutOfService RW On/Off

11

612 SCH12 OutOfService RW On/Off

12

613 SCH13 OutOfService RW On/Off

13

614 SCH14 OutOfService RW On/Off

14

615 SCH15 OutOfService RW On/Off

15

616 SCH16 OutOfService RW On/Off

16

Table 58. Schedule OutOfService registers.

Sample Packets

Table 59 is an example of a request for SCH
OutOfService

status

instance

Reg601–Reg616

(Function 1, SCH1–16 in map). Note that SCH
OutOfService Status Reg4208– Reg4201 is shown as hex
value AB or binary 1010 1011, while Reg4201 is the LSB
and Reg4208 is the MSB. Reg4201 is SCH01
OutOfService Status.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

01 Function

01

Register Address Hi

02 Byte Count

02

Register Address Lo 58 SCH OutOfService 608–601 AB
Quantity of SCH Hi

00 SCH OutOfService 616–609 AA

Quantity of SCH Lo

10 Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 59. Sample packets for request for SCH OutOfService status.