Analog variables (av) – physical input setup, A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 22

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Physical Input Registers-Analog Variable(AV)

16

Analog Variables (AV) –
Physical Input Setup


The input value behavior of the two remote
(Daylight Optimization) boards can be
altered by adjusting the parameters

represented by the Analog Variables
AV601-AV632 & AV701-AV732.


Analog Variable (AV) Object – (Registers 1301-1364 & 1401-1464)

The Analog Input Parameters (i.e. AV Present Value) are mapped as follows (Table 24):

Input

Set Point (SP)
Registers

Proportional Band
Registers

Reset Rate (RR)
Registers

Output Value (OP)*
Register

AI-601

1301 – 1302 (AV601)

1317 – 1318 (AV609)

1333 – 1334 (AV617)

1349 – 1350 (AV625)

AI-602

1303 – 1304 (AV602)

1319 – 1320 (AV610)

1335 – 1336 (AV618)

1351 – 1352 (AV626)

AI-603

1305 – 1306 (AV603)

1321 – 1322 (AV611)

1337 – 1338 (AV619)

1353 – 1354 (AV627)

AI-604

1307 – 1308 (AV604)

1323 – 1324 (AV612)

1339 – 1340 (AV620)

1355 – 1356 (AV628)

AI-605

1309 – 1310 (AV605)

1325 – 1326 (AV613)

1341 – 1342 (AV621)

1357 – 1358 (AV629)

AI-606

1311 – 1312 (AV606)

1327 – 1328 (AV614)

1343 – 1344 (AV622)

1359 – 1360 (AV630)

AI-607

1313 – 1314 (AV607)

1329 – 1330 (AV615)

1345 – 1346 (AV623)

1361 – 1362 (AV631)

AI-608

1315 – 1316 (AV608)

1331 – 1332 (AV616)

1347 – 1348 (AV624)

1363 – 1364 (AV632)

AI-701

1401 – 1402 (AV701)

1417 – 1418 (AV709)

1433 – 1434 (AV717)

1449 – 1450 (AV725)

AI-702

1403 – 1404 (AV702)

1419 – 1420 (AV710)

1435 – 1436 (AV718)

1451 – 1452 (AV726)

AI-703

1405 – 1406 (AV703)

1421 – 1422 (AV711)

1437 – 1438 (AV719)

1453 – 1454 (AV727)

AI-704

1407 – 1408 (AV704)

1423 – 1424 (AV712)

1439 – 1440 (AV720)

1455 – 1456 (AV728)

AI-705

1409 – 1410 (AV705)

1425 – 1426 (AV713)

1441 – 1442 (AV721)

1457 – 1458 (AV729)

AI-706

1411 – 1412 (AV706)

1427 – 1428 (AV714)

1443 – 1444 (AV722)

1459 – 1460 (AV730)

AI-707

1413 – 1414 (AV707)

1429 – 1430 (AV715)

1445 – 1446 (AV723)

1461 – 1462 (AV731)

AI-708

1415 – 1416 (AV708)

1431 – 1432 (AV716)

1447 – 1448 (AV724)

1463 – 1464 (AV732)

Table 24 Analog Variable Registers


*Setting SP= -1 allows writing of the Output Value.
**Note: do NOT write to any of these registers without specific knowledge of the consequence




Analog Variable (AV) Properties

Each AV object exposes the following properties (Table25) via Function codes 3/6/16.

Offset Modbus Regs DB size

Property

Format

Range

Type

0

1301 – 1302 FLOAT Hi Value

0 – 65535

RW

2 registers per AV

Table 25. Analog Variable Properties