A series, Sample packets – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 48

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Compact Event Log

42

Sample Packets

Following are examples of function requests to the
compact event log.

Ask for Compact Event Log Event #1

Table 81 is an example of a request for Event#1
Reg20007–Reg20014 (Function 4, CEL1 in map).
The response is as follows:

Reg20007–Reg20008 Time: 16:37:27.60
Reg20009–Reg20010 Date: Wed May 26, 2004
Reg200011 Event Type: 0x003D, Device Reset
Reg20012 Event Argument: 0x0000
Reg20013–Reg20014 Event Object Ref: 0x00090064,

DEV100

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

04 Function

04

Register Address Hi

4E Byte Count

10

Register Address Lo

26 Register Value Hi (20007) 10

Registers Hi

00 Register Value Lo (20007) 25

Registers Lo

08 Register Value Hi (20008) 1B

Packet CRC Hi

Register Value Lo (20008) 3C

Packet CRC Lo

Register Value Hi (20009) 03

Register Value Lo (20009) 1A

Register Value Hi (20010) 05

Register Value Lo (20010) 68

Register Value Hi (20011) 00

Register Value Lo (20011) 3D

Register Value Hi (20012) 00

Register Value Lo (20012) 00

Register Value Hi (20013) 00

Register Value Lo (20013) 09

Register Value Hi (20014) 00

Register Value Lo (20014) 64

Packet CRC Hi

Packet CRC Lo

Table 81. Sample packets for request for compact event log event #1.

Ask for Compact Event Log Total Events

Table 82 is an example of a request for Compact Event
Log Total Events, Alarm Output Ref Reg20001–Reg20005.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

04 Function

04

Register Address Hi

4E Byte Count

06

Register Address Lo

20 Register Value Hi (20001) 00

Registers Hi

00 Register Value Lo (20001) 00

Registers Lo

05 Register Value Hi (20002) 00

Request

Response

Field Name

Hex Field Name

Hex

Packet CRC Hi

Register Value Lo (20002) 12

Packet CRC Lo

Register Value Hi (20003) 00

Register Value Lo (20003) 64

Register Value Hi (20004) 00

Register Value Lo (20004) 05

Register Value Hi (20005) 00

Register Value Lo (20005) 44

Packet CRC Hi

Packet CRC Lo

Table 82. Sample packets for request for compact event log total events.

The response is as follows:

Reg20001–Reg 20002 Total Event: 0x00000012, 18

decimal

Reg20003–Reg20005

Alarm

Output:

Ref.

0x006400050044, 100.BO68 (Alarm Relay)

Ask for Compact Event Log Nonexistent Event

Table 83 is an example of a request for Event #21,
Reg20173–Reg20180, which does not exist. The response
is an error return for invalid data value, since there are
only 18 events in the list.

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

04 Error Code

84

Register Address Hi

4E Exception Code

03

Register Address Lo

CC Packet CRC Hi

Registers Hi

00 Packet CRC Lo

Registers Lo

08

Packet CRC Hi

Packet CRC Lo

Table 83. Sample packets for request for nonexistent event.



Compact Event Log (CEL) – Setup (Registers 60001 –
60008)
Table 84 shows the registers to set up alarm events and
alarm output reference.










Advertising