© Gardner Denver Deutschland GmbH

Connections for braking resistor

Terminal assignment for braking chopper

Terminal no.

Designation

(Terminal) assignment

1

B+

Connection of braking resistor (+)

2

B-

Connection of braking resistor (-)

Control terminals

Control terminals of the standard application card

NOTICE

Risk of coupling of external signals!
 Use shielded control wires.

1. Pass the required control wires through the threaded cable glands into the

housing.

2. Connect the control wires according to the picture and/or table. To do this,

use shielded control wires.

3. Put the lid on the housing of the drive controller and screw it in place.

Terminal assignment X5 of the standard application card

Terminal no. Designation

(Terminal) assignment

1

24 V In

External power supply

2

GND (Ground)

Ground

3

24 V Out

Internal power supply

4

GND (Ground)

Ground

5

24 V Out

Internal power supply

6

Dig. In 1

fixed frequency 1/3 (parameter 1,100)

Software release (parameter 1,131)

7

Dig. In 2

fixed frequency 2/3 (parameter 1,100)

8

Dig. In 3

Fault reset (parameter 1,180)

9

Dig. In 4

External error (parameter 5,010)

10

En -HW (release)

Hardware release

11

Dig. Out 1

Ready (parameter 4,150)

12

Dig. Out 2

Operation (parameter 4,170)

13

A. Out 0 ... 20 mA

Actual frequency value (parameter
4,100)

14

10 V Out

For external voltage divider

5.3.5