Installation – Elmo Rietschle 2FC4...-1CB User Manual

Page 25

Advertising
background image

Installation

5

© Gardner Denver Deutschland GmbH

25

/

74

05.2014 · 610.00260.40.000

Terminal no. Designation

(Terminal) assignment

15

A. Out 0 ... 10 V

Actual frequency value (parameter
4,100)

16

A GND (Ground 10 V)

Ground

17

A. In 1

External Setpoint source (parameter
1,130)

18

A GND (Ground 10 V)

Ground

19

A. In 2

Actual PID value (parameter 3,060)

20

A GND (Ground 10 V)

Ground

Terminal assignment X6 (relay 1)

Terminal no. Designation

(Terminal) assignment

1

COM

Centre contact relay 1

2

NO

Normally open contact relay 1

3

NC

Normally closed contact relay 1

In the factory setting, relay 1 is programmed as "fault relay" (parameter
4,190).

Terminal assignment X7 (relay 2)

Terminal no. Designation

(Terminal) assignment

1

COM

Centre contact relay 2

2

NO

Normally open contact relay 2

3

NC

Normally closed contact relay 2

In the factory setting, relay 2 is programmed as "fault relay" (parameter
4,210).

Wiring diagram

Control terminals

The drive controller is ready for operation after connection to a 400 V AC power
supply (to the terminals L1 to L3) or after connection to a 565 V DC power supply
(to the terminals L1 and L3).

Alternately, there is the option to put the drive controller in operation by connect-
ing an external 24 V voltage.

The required presetting is described in the chapter "System parameters".

5.3.7