Parameters

610.00260.40.000 · 05.2014

44

/

74

© Gardner Denver Deutschland GmbH

1,180

Acknowledgement function

Unit: integer

Relationship to
parameter:
1.181
1.182

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 5

Def: 3

Selects the source for the error acknowledgement.
Errors can only be acknowledged if the error is no longer pre-
sent.
Certain errors can only be acknowledgement by switching the
controller on and off, see list of errors.
Automatic acknowledgement via parameter 1,181
0 = no manual acknowledgement possible
1 = increasing slope at the digital input 1
2 = increasing slope at the digital input 2
3 = increasing slope at the digital input 3
4 = increasing slope at the digital input 4
5 = membrane keyboard (Reset button)

1,181

Automatic acknowledgement

function

Unit: s

Relationship to
parameter:
1.180
1.182

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 1000000

Def: 0

Besides the acknowledgement function (1,180), automatic fault
acknowledgement can also be selected.
0 = no automatic acknowledgement
> 0 = time for the automatic reset of the error in seconds

1,182

Automatic acknowledgement

count

Unit:

Relationship to
parameter:
1.180
1.181

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 500

Def: 5

In addition to the automatic acknowledgement function (1,181),
the maximum number of automatic acknowledgements can be
limited here.
0 = no limit for the number of automatic acknowledgements
> 0 = number of maximum automatic acknowledgements al-
lowed

Fixed frequency

This mode must be selected in parameter 1,100, see also selection of the operat-
ing mode.

2.050

Fixed frequency mode

Unit: Integer

Relationship to
parameter:
1.100
2.051 – 2.057

Parameter HB:


Transfer

status:


min: 0

Intrinsic value
(to be en-
tered!
)

max: 3

Def: 1

Selection of the digital inputs used for the fixed frequencies.
0 = digital input 1 (fixed frequency 1) (2,051)
1 = digital input 1, 2 (fixed frequencies 1 - 3) (2,051 - 2,053)
2 = digital input 1, 2, 3 (fixed frequencies 1 - 7) (2,051 - 2,057)
3 = membrane keyboard (button 1 = fixed frequency 1 / button 2
= fixed frequency 2)

7.3.2