Error detection and elimination

610.00260.40.000 · 05.2014

62

/

74

© Gardner Denver Deutschland GmbH

List of errors and system errors

When an error occurs, the inverter switches off; for the corresponding error num-
bers, refer to the flash code table or the PC tool.

Error messages can only be acknowledged when the error is no longer pre-
sent.

!

Error messages can be acknowledged as follows:

1. Digital input (programmable)

2. via the hand-held unit MMI

3. Automatic acknowledgement (parameter 1,181)

4. Switching the device on and off

5. via fieldbus (CANOpen, Profibus DP, EtherCAD)

Below is a list of possible error messages. For errors not listed here, please con-
tact the manufacturer.

Error detection

No. Error name

Error description

Possible cause / remedy

1

Low voltage 24 V application

Supply voltage of the applica-
tion is less than 15 V

Overload of the 24 V supply

2

Over-voltage 24 V application

Supply voltage of the applica-
tion is greater than 31 V

Internal 24 V supply is not OK or
external power supply is not OK

3

Version error of client PLC

The version of the client PLC
does not match the device
firmware

Check the version numbers of
the customer PLC and device
firmware

4 Communication

applica-

tion<>performance

The internal communication
between the application and
power printed circuit board is
out of order

EMC interference

5 Parameters

distributor

The internal distribution of the
parameters during the initialisa-
tion has failed

Parameter set is incomplete

6 Timeout

performance

The

power unit does not re-

spond

Operation with 24 V without
power supply

7

Cable breakage analogue input
1 (4 - 20 mA / 2 - 10 V)

Current or voltage is less than
the lower limit of the analogue
input 1 (this error monitoring is
activated by setting the parame-
ter 4,021 to 20%)

Cable breakage, defective ex-
ternal sensor

8

Cable breakage analogue input
2 (4 - 20 mA / 2 - 10 V)

Current or voltage is less than
the lower limit of the analogue
input 2 (this error monitoring is
activated by setting the parame-
ter 4,021 to 20%)

Cable breakage, defective ex-
ternal sensor

9

Blocking detection

The drive shaft of the motor is
blocked. 5.080

Remove blockage

10

Overtemperature of drive con-
troller application

Internal temperature too high

Insufficient cooling, low speed
and high torque, clock fre-
quency too high

11

Bus timeout

No response from the bus de-
vice or HAND-HELD UNIT MMI /
PC

Check bus wiring

12 Confirmation

error

The number of max. automatic
acknowledgements (1,182) has
been exceeded

Check the error history and
eliminate errors

8.2