Parameters – Elmo Rietschle 2FC4...-1CB User Manual

Page 55

Advertising
background image

Parameters

7

© Gardner Denver Deutschland GmbH

55

/

74

05.2014 · 610.00260.40.000

Power parameters

Motor data

33.001

Motor type

Unit: Integer

Relationship to
parameter:
33.010

Parameter HB:

S. xy

Transfer

status:

1

min: 1

Intrinsic value
(to be en-
tered!
)

max: 2

Def: 1

Selection of the motor type
1 = Asynchronous motor
2 = Synchronous motor
Depending on the motor type selected, the corresponding pa-
rameters are displayed.
The control mode (parameter 34,010) must also be chosen ac-
cordingly.

33.015

R optimisation

Unit: %

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

1

min: 0

Intrinsic value
(to be en-
tered!
)

max: 200

Def: 100

If necessary, the start-up behaviour can be optimised using this
parameter.

33.031

Motor current

Unit: A

Relationship to
parameter:
5.070

Parameter HB:

S. xy

Transfer

status:

1

min: 0

Intrinsic value
(to be en-
tered!
)

max: 150

Def: Type-
specific

Hereby, the rated motor current I

M,N

is set for either star or delta

connection.

33.032

Motor power

Unit: W

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

1

min: 0

Intrinsic value
(to be en-
tered!
)

max: 55000

Def: Type-
specific

A power value [W] P

M,N

that is equal to the rated motor power

must be set here.

33.034

Motor speed

Unit: rpm

Relationship to
parameter:
34.120
5.075

Parameter HB:

S. xy

Transfer

status:

1

min: 0

Intrinsic value
(to be en-
tered!
)

max: 10000

Def: Type-
specific

Here, the rated motor speed n

M,N

from the type plate data of the

motor should be entered.

33.035

Motor frequency

Unit: Hz

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

1

min: 40

Intrinsic value
(to be en-
tered!
)

max: 100

Def: Type-
specific

The rated motor frequency f

M,N

is set here.

7.4

7.4.1