7

Parameters

610.00260.40.000 · 05.2014

48

/

74

© Gardner Denver Deutschland GmbH

4.021/4.051

AIx Norm. Low

Unit: %

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 100

Def: 0

Specifies the minimum value of the analogue inputs as a per-
centage of the final range value.
Example:
0... 10V or 0... 20 mA = 0 %... 100%
2... 10V or 4... 20mA = 20%... 100%

4.022/4.052

AIx Norm. High

Unit: %

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 100

Def: 100

Specifies the maximum value of the analogue inputs as a per-
centage of the final range value.
Example:
0…10V or 0…20mA = 0%…100%
2…10V or 4…20mA = 20%…100%

4.023/4.053

Alx backlash

Unit: %

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 100

Def: 0

Backlash as percentage of final range value of the analogue
inputs.

4.024/4.054

AIx filtering time

Unit: s

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

2

min: 0,02

Intrinsic value
(to be en-
tered!
)

max: 1,00

Def: 0

Filtering time of the analogue inputs in seconds.

4.030/4.060

Alx function

Unit: Integer

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 1

Def: 0

Function of the analogue inputs ½.
0 = analogue input
1 = digital input