Parameters – Elmo Rietschle 2FC4...-1CB User Manual

Page 51

Advertising
background image

Parameters

7

© Gardner Denver Deutschland GmbH

51

/

74

05.2014 · 610.00260.40.000

Digital outputs

For the digital outputs 1 and 2 (DOx - illustration DO1/DO2)

4.150/4.170

DOx function

Unit: Integer

Relationship to
parameter:
4.151/4.171
4.152/4.172

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 50

Def:
4.150: 18
4.170: 19

Selection of the process variable to which the output should
switch.
0 = not assigned / integrated soft - PLC
1 = intermediate circuit voltage
2 = mains voltage
3 = motor voltage
4 = motor current
5 = actual frequency value
6 = -
7 = -
8 = IGBT temperature
9 = inner temperature
10 = error (NO)
11 = error inverted (NC)
12 = output stage release
13 = digital input 1
14 = digital input 2
15 = digital input 3
16 = digital input 4
17 = ready for operation
18 = ready
19 = operation
20 = ready for operation + ready
21 = ready for operation + ready + operation
22 = ready + operation
23 = motor power
24 = torque
25 = field bus
26 = analogue input 1 (above V3.60)
27 = analogue input 2 (above V3.60)
28 = PID setpoint (above V3.60)
29 = PID feedback (above V3.60)
50 = motor current limit active

4.151/4.171

DOx On

Unit:

Relationship to
parameter:
4.150/4.170

Parameter HB:

S. xy

Transfer

status:

2

min: -10000

Intrinsic value
(to be en-
tered!
)

max: 10000

Def: 0

If the set process variable exceeds the switch-on limit, the out-
put is set to 1.

4.152/4.172

DOx Off

Unit:

Relationship to
parameter:
4.150/4.170

Parameter HB:

S. xy

Transfer

status:

2

min: -10000

Intrinsic value
(to be en-
tered!
)

max: 10000

Def: 0

If the set process variable falls below the switch-on limit, the
output is set to 0.

7.3.8