Parameters – Elmo Rietschle 2FC4...-1CB User Manual

Page 45

Advertising
background image

Parameters

7

© Gardner Denver Deutschland GmbH

45

/

74

05.2014 · 610.00260.40.000

2.051 – 2.057

Fixed frequency

Unit: Hz

Relationship to
parameter:
1.020
1.021
1.100
1.150
2.050

Parameter HB:


Transfer

status:


min: -400

Intrinsic value
(to be en-
tered!
)

max: +400

Def:
2.051: 34
2.052: 67
2.053: 50

The frequencies that should be output at the digital inputs 1 - 3
set in parameter 2,050, depending on the switching pattern.
See fixed frequency, Explanation of operating modes [➙ 36].

Motor potentiometer

This mode must be selected in parameter 1,130. This function can be used both
as a setpoint source for the frequency setting mode as well as for the PID process
controller.

2.150

MOP digital input

Unit: Integer

Relationship to
parameter:
1.130
4.030
4.050

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 8

Def: 0

Selection of the source to increase and decrease the setpoint.
0 = digital input 1 + / digital input 2 -
1 = digital input 1 + / digital input 3 -
2 = digital input 1 + / digital input 4 -
3 = digital input 2 + / digital input 3 -
4 = digital input 2 + / digital input 4 -
5 = digital input 3 + / digital input 4 -
6 = analogue Input 1 + / analogue Input 2 - (must be selected in
parameter 4,030 / 4,050)
7 = DRIVE CONTROLLER soft PLC
8 = membrane keyboard (button 1 - / button 2 +)

2.151

MOP increment

Unit: %

Relationship to
parameter:
1.020
1.021

Parameter HB:

S. xy

Transfer

status:

2

min: 0

Intrinsic value
(to be en-
tered!
)

max: 100

Def: 1

Increment at which the setpoint value is to be changed per key-
stroke.

2.152

MOP increment time

Unit: s

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

2

min: 0,02

Intrinsic value
(to be en-
tered!
)

max: 1000

Def: 0,04

Specifies the time in which the setpoint is summed up with per-
manently present signal.

2.153

MOP response time

Unit: s

Relationship to
parameter:

Parameter HB:

S. xy

Transfer

status:

2

min: 0,02

Intrinsic value
(to be en-
tered!
)

max: 1000

Def: 0,3

Specifies the time until the present signal is considered to be
permanent.

7.3.3