Installing the coupled bonding conductor, Installing coupled bonding conductor wires – Avaya 03-300686 User Manual

Page 58

Advertising
background image

MDF connections to stations and the public switched telephone network

58 Installing and Connecting the MDF and Telephones

Installing the coupled bonding conductor

The coupled bonding conductor (CBC) provides a path to ground for transient energy (for
instance, lightning) by virtue of mutual inductance between itself and exposed telcom cables.
The CBC connects on one end to an approved single-point ground, runs adjacent to the telcom
cable, and connects on the other end to the CBC terminal bar at the main distribution frame
(MDF).
The CBC can be:

a 10 AWG (#25) (6 mm

2

) wire tie wrapped to the exposed telecom cables

a metal cable shield around the exposed cables, or

six spare pairs form the exposed cable

A minimum of 12" spacing should be maintained between the CBC and other power, ground, or
non-exposed communications cables.

Installing coupled bonding conductor wires

To install coupled bonding conductor wires:

1. At the DC power cabinet, connect a 10 AWG (#25) (6 mm

2

) ground wire to the Ground

Discharge Bar. See

Figure 27: Typical power and ground for a DC power cabinet

on

page 59.

2. Route the 10 AWG (#25) (6 mm

2

) ground wire to the CBC ground terminal bar at the MDF.

3. Tie wrap the ground wire to the inside wiring cable.