MDF connections to stations and the public switched telephone network

60 Installing and Connecting the MDF and Telephones

To provide the coupled bonding protection:

1. Cut a 10 AWG (#25) (2.5 mm

2

) wire long enough to reach from the equipment room

single-point ground block (or DC power Ground Discharge Bar) to the MDF CBC block. See

Figure 28: Coupled Bonding Conductor

on page 61.

2. Connect one end of the 10 AWG (#25) (2.5 mm

2

) wire to the single-point ground block (or

Ground Discharge Bar).

3. Route the wire next to the 25-pair cables connecting to the trunk/auxiliary (purple) field.

4. Tie wrap the 10 AWG (#25) (2.5 mm

2

) wire to the 25-pair cables.

5. Connect the 10 AWG (#25) (2.5 mm

2

) wire to the MDF CBC ground block.

6. Repeat the above steps for each CBC ground wire installed.