Installing and wiring telephones and trunks

94 Installing and Connecting the MDF and Telephones

The 4-type protector is the preferred device. For installations not using primary protection,
4-type protectors should always be used. When the 3-type protector is already installed, a
separate sneak current protector is required.
The multi-pair protector units and the off-premises cabling must be locally engineered.
Connected multi-pair protector units (female 25-pair connector) are recommended.

Table 15: Analog line circuit protectors

shows the recommended protectors.

For catalogs and ordering information, go to the Avaya Cable Management Systems for Service
Providers Web site (

http://connectivity.avaya.com/exchangemax/

) and click Products &

Solutions.

Telephone restrictions for exposed environments

Analog telephones connected to TN746B Analog Line circuit packs cannot be installed in an
exposed environment.

Digital Out-of-Building Telephone Protection

Digital out-of-building telephones require protection at both building entrances. The 4C3S-75
Enhanced Protector and the ITW Linx Enhanced Protector can be used to protect digital
telephones and digital line circuit packs. These units provide primary and sneak current
protection. The 4C3S-75 is equipped with a heat coil for sneak current protection, and the ITW
Linx is equipped with replaceable fuses for sneak current protection.

Note:

Note:

The TN2181 16-port, 2-wire digital line circuit pack may not be approved for
some out-of-building uses. Contact your Avaya representative for more
information.

Table 15: Analog line circuit protectors

Primary

*

*. The 3-type protectors should be used only if they are already part

of the existing protection system. A sneak current protector is
always required when a 3-type primary protector is used.

Primary
(with heat coil)

Sneak current
protectors

*

3B1A (carbon)

4B1C (carbon)

220029 Fuse

3B1E-W

(wide gap gas tube)

4B1E-W

(wide gap gas tube)

SCP-1

3C1S

(solid state)

4C1S

(solid state)