Installing the coupled bonding conductor

Issue 3 January 2008

59

Figure 27: Typical power and ground for a DC power cabinet

Note:

Note:

For a high-rise building, connect the CBC to an approved building ground on
each floor.

Note:

Note:

Below is general information for installing the CBC in all installations having
exposed facilities.

Figure notes:

1. Approved Ground
2. 1 AWG Ground Wire
3. CBC Ground Terminal Bar at the

MDF (if used)

4. System Single-point Ground

Discharge Bar

5. DC Power Cabinet J58890R or

new DC system

6. Ground Wire for Battery (+)
7. Battery Frame Ground
8. DC Battery Cabinet
9. Main AC Supply (AC Mains)

10. AC to DC power cabinet

11. To Next DC-powered Media Gateway

12. DC load circuit breakers

50A

50A

50A

50A

-48

VDC

-48 V

-48 V

-48 V

-48 V RTN

-48 V RTN

-48 V RTN

MCC

MCC

MCC

10 AWG

RED

10 AWG

6 AWG

AC

phase

AC

phase

10 AWG

10 AWG
10 AWG

10 AWG

BLACK

RTN

cydfdc3i KLC 050304

BLACK

10 AWG

RED

BLACK

10 AWG

RED

10 AWG

RED

10 AWG

BLACK

Batter

y

circuit

breaker

+

-

LVD

Rectifiers

DC power

from rectifiers

+

-

Green/Yellow
Green/Yellow
Green/Yellow

1

2

3

4

5

6

7

8

9

10

11

12