Agilent Technologies E1300B User Manual

Page 139

Advertising
background image

:DOWNload:CHECked

:SADDress

DIAGnostic:CHECked:DOWNload:SADDress < address> ,< data> writes data
to non-volatile User RAM at a single address specified by address using error
correction. It can also write to devices with registers in the A16 address space.

Parameters

Parameter

Name

Parameter

Type

Range of

Values

Default

Units

address

numeric

0 to 16,777,215 (# HFFFFFE)

none

data

arbitrary block

program data

See "Parameter Types", in the

beginning of this chapter

none

Comments

This command is typically used to send data to a device which accepts
data at a single address. It is the only way to send binary data to single
addresses over a serial (RS232C) line.

Most computers terminate an OUTPUT, PRINT, or WRITE statement
with a carriage return or carriage return and line feed. These
End-Of-Line characters must be either accounted for (NRAM segment
sized to accommodate them), or suppressed using an appropriate
IMAGE or FORMAT statement. Some helpful methods:

Control the End-Of-Line characters with format statements.
Use the Definite Length Arbitrary Block Program Data format (see

example) to send your data rather than the Indefinite Length
Arbitrary Block Program Data
format.

A register address in A16 address space can be determined by:

1FC00

16

+ (LADDR * 64) + register_number

where 1FC000

16

is the base address in the System Instrument A16 space,

LADDR is the device logical address, 64 is the number of address bytes
per device, and register_number is the register to which the data is
written.

If the device is an A24 device, the address can be determined using the
VXI:CONF:DLISt command to find the base address in A24, and then
adding the register_number to that value. A24 memory between address
200000

16

and address E00000

16

is directly addressable by the Controller.

Address may be specified in decimal, hex (# H), octal (# Q), or binary
(# B) formats. DOWNload is done by word (16 bit) access so address
must be even.

Related Commands: DIAG:UPLoad:SADDress?

DIAGnostic :DOWNload:CHECked :SADDress

System Instrument Command Reference 7-11