Exception status outputs, Diagnostic sub-functions, Table 45 – Vaisala HMT330 User Manual

Page 206: Hmt330 exception status outputs, Table 46, Hmt330 modbus diagnostics

Advertising
background image

User's Guide _______________________________________________________________________

204 __________________________________________________________________ M210566EN-K

Other configuration settings are not usually needed and are not available
using the Modbus interface. The service cable must be used to change
other configuration settings if needed.

Exception Status Outputs

Exception status outputs (read with function code 07) tell the summary of
the HMT330 transmitter status as described in Table 45 below.

Table 45

HMT330 Exception Status Outputs

Output

Name

Description

0 (0x01)

Fault status

1 = No errors

1 (0x02)

Online status

1 = Online data available

Status information is available also with register access; see section
Status Registers (Read-Only) on page 202.

Diagnostic Sub-Functions

HMT330 supports some of the Modbus diagnostic functions described in
the Modbus Application Protocol Specification V1.1b. These diagnostic
functions are accessed with function code 08. See Table 46 below for
details.

Table 46

HMT330 Modbus Diagnostics

Code

Sub-Function Name

Notes

00 (0x00)

Return Query Data

01 (0x01)

Restart Communications
Option

Cancels the “Listen Only” mode.

Data field must be set to “00 00”
for Restart Communications
Option. Sub-Function 01 with
data field “FF 00” is rejected.

02 (0x02)

Return Diagnostic Register

Non-zero if there are active
transmitter errors.

For same error information, see
status registers 0516 and 0517.
The value of the Diagnostic
Register is a logical OR of these
two status registers.

04 (0x04)

Force Listen Only Mode

Puts device “off-line”

10 (0x0A)

Clear Counters and
Diagnostic Register

Diagnostic Register cannot be
cleared

11 (0x0B)

Return Bus Message Count

Total number of messages seen
on the bus/interface

12 (0x0C)

Return Bus Communication
Error Count

Number of messages with bad
Modbus RTU CRC or Modbus
TCP frame