Campbell Scientific AP200 CO2/H2O Atmospheric Profile System User Manual

Page 72

Advertising
background image

Appendix B. AP200 Diagnostics

Second, because it is an average over time, it is impossible to tell which bits

are set. For example, an average of 4.0 could mean that bit 3 (numeric value =

4) is set all the time or it could mean that bit 4 (numeric value = 8) is set half

the time, etc. For this reason,

diag_AP200_Avg can indicate only whether or

not there was a problem (nonzero value) or not. If

diag_AP200_Avg is

nonzero, use the time series of

diag_AP200 in the RawData table to diagnose

the problem.

The following sections give details on each of the diagnostic bits.

Bit 1:

Battery voltage is too low

If bit 1 of

diag_AP200 is set, this indicates the power source for the AP200 has

dropped below the acceptable voltage limit. This triggers the AP200 to power

down as much of the system as possible to protect the user’s battery from a

deep discharge that might damage the battery. The pump, valves, pump and

valve heaters and fans, and intake heaters will all be turned off. The IRGA is

powered directly, so it cannot be turned off. The AP200 will power up again

when the supply voltage reaches an acceptable level.

There are two system configuration variables,

BATT_LOLIMIT and

BATT_DEADBAND, that determine the shut-down and turn-on voltage (see

Section 5.4.1, System Configuration Variables).

To confirm the problem, verify public variable

batt_volt_LOW = True. This

variable is set to

True if the battery voltage falls below the shutoff limit:

batt_volt < BATT_LOLIMIT

Note that

batt_volt_LOW will remain True until the supply voltage reaches

the turn-on voltage:

batt_volt > BATT_LOLIMIT + BATT_DEADBAND

The purpose of the deadband (the gap between the shut-down voltage and the

turn-on voltage) is to protect the AP200 from repeated power cycles when the

battery voltage is very near the shut-down limit. Note that for troubleshooting

purposes, if

batt_volt_LOW = True and batt_volt is in the deadband,

manually set

batt_volt_LOW = False. This will let the AP200 power up.

If this does not work, measure the voltage at the AP200 power input terminals,

and compare this to

batt_volt. Note that batt_volt is measured in the

datalogger which has a diode for reverse voltage protection. The actual voltage

at the input terminals will be approximately 0.3 volts higher than the value

reported by

batt_volt.

The AP200 supply voltage must be 10.0 Vdc to 16.0 Vdc. See Section 4.3.2,

System Enclosure, for details on the power required, especially the extra power

required for a cold startup.

B-2

Advertising