Appendix f. valve sequence timing, Ee appendix f – Campbell Scientific AP200 CO2/H2O Atmospheric Profile System User Manual

Page 95

Advertising
background image

Appendix F. Valve Sequence Timing

The AP200 has two valve sequences: the profile sequence and the calibration

(zero/span) sequence. The AP200 will run the majority of the time in the

profile sequence, cycling through the profile inlets in order from one to the

number of levels selected (4 to 8). If configured for automatic zero/span, then

the AP200 will periodically run the calibration sequence before returning to the

profile sequence. The timing of the valve switching depends on settings of the

following system configuration variables (see Section 5.4.1, System

Configuration Variables, for details on the system configuration variables):

LEVELS_USED
MEASURE_TANKS
AUTO_ZEROSPAN
CAL_INTERVAL
CAL_TIMEOFFSET

Profile Sequence

The profile sequence cycles through the profile inlets in order, starting at 1, and

ending at the value of

LEVELS_USED. This cycle repeats until it is

interrupted for an automated calibration sequence (if this feature is enabled) or

until the sequence is stopped by the user.

The AP200 has pre-programmed parameters that determine the timing of the

profile sequence. These timing parameters allow for at least 15 s on each level,

with 10 s omitted to allow the CO

2

and H

2

O concentrations to equilibrate, and

5 s included in the average. In addition to these constraints, the timing

parameters depend on the number of levels used (

LEVELS_USED) to give an

integer number of complete cycles in each half-hour averaging period. As

shown in TABLE F-1, the timing for 4, 6, or 8 levels simply use these

minimum values, giving 15, 20, or 30 cycles per half hour. The times are

extended slightly for 5 or 7 levels to give integer number of cycles per half

hour.

TABLE F-1. Profile Sequence-timing Variables

Number

of Levels

Time on

Level (s)

Omitted

Time (s)

Averaged

Time (s)

Cycle

Time (s)

Cycles/

Half Hour

4

15

10

5

60

30

5

18

12

6

90

20

6

15

10

5

90

20

7

18/17*

12/11*

6

120

15

8

15

10

5

120

15

*18 s on level 1 with 12 s omitted; 17 s with 11 s omitted for the rest of the levels

F-1