12.2 Serial RS-232 media

NOTE:

Before using the Maestro serial port for MODBUS purposes, you MUST disconnect it
from the command interpreter by sending the

rsauto(0)

command from the terminal

and switching power supply to OFF/ON.

12.2.1 Communication parameters for ASCII or RTU

MODBUS address (view paragraph 12.1.1)

Serial port

Serial port identifier

Default port value "COM1"

Baud rate

Port baud rate in bps (typically 1200-115200 ,maximum Value depends on UART
hardware)

Default value - 38400

Data bits

Port data bits: (for RTU Must be SER_DATABITS_8)

Default value - 8

Stop bits

Port stop bits: (typically value 1 - 2)

Default value - 1

Parity

Port parity: no parity, odd parity or even parity

Default value - no parity

12.3 MODBUS Master functionality

Master Function Call

Modicon

®

Register Table

readCoil*, readCoils,

writeSingleCoil, writeMultipleCoils

0:00000

readDiscreteInput*, readDiscreteInputs 1:00000

readInputRegister*, readInputRegisters 3:00000

readHoldingRegister*,
readHoldingRegisters,

writeSingleRegister,

writeMultipleRegisters,

maskWriteRegister, readWriteRegisters

4:00000

* - for command interpreter only

Table 12-2: MODBUS Master Object Data Access functionality