Mc_home_limit_switch – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 119

Advertising
background image

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

105

Motion Control with PTO and PWM Chapter 7

3.

Move to the configured home position. The mechanical home position
recorded during moving right sequence, plus the home offset configured
for the axis in the Connected Components Workbench software.

Scenario 4: Moving part at left (negative) side of Lower Limit switch before
homing starts

In this case, the homing motion fails and moves continuously to the left until
drive or moving part fails to move. User needs to make sure the moving part at the
proper location before homing starts.

MC_HOME_LIMIT_SWITCH

For Homing against Lower Limit switch, one positive home offset can be
configured; for Homing against Upper Limit switch, one negative home offset
can be configured.

MC_HOME_LIMIT_SWITCH (1) homing procedure performs a homing
operation against Limit switch. The actual motion sequence is dependent on the
limit switch configuration and the actual status for the switch before homing
starts—that is, when the MC_Home function block is issued.

Scenario 1: Moving part at right (positive) side of Lower Limit switch before
homing starts

The homing motion sequence for this scenario is as follows:

1.

Moving part moves to its left side (in negative direction);

2.

When Lower Limit switch is detected, the moving part decelerates to stop,
or stops immediately, according to Limit Switch Hard Stop configuration;

3.

Moving part moves back (in positive direction) in creep velocity to detect
Lower Limit switch On

→ Off edge;

4.

Once Lower Limit switch On

→ Off edge is detected, record the position

as mechanical home position, and decelerate to stop;

5.

Move to the configured home position. The mechanical home position
recorded during moving back sequence, plus the home offset configured
for the axis through the Connected Components Workbench software.

Scenario 2: Moving part on Lower Limit switch before homing starts

The homing motion sequence for this scenario is as follows:

IMPORTANT

If Lower Limit switch is not configured as Enabled,
MC_HOME_LIMIT_SWITCH (1) homing will fail (Error ID:
MC_FB_ERR_PARAM).