Grounding your analog cable, Wiring examples, Grounding your analog cable wiring examples – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 52: Sink output wiring example

Advertising
background image

38

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Chapter 4 Wire Your Controller

Grounding Your Analog Cable

Use shielded communication cable (Belden #8761). The Belden cable has two
signal wires (black and clear), one drain wire, and a foil shield. The drain wire and
foil shield must be grounded at one end of the cable.

Wiring Examples

Examples of sink/source, input/output wiring are shown below.

IMPORTANT

Do not ground the drain wire and foil shield at both ends of the cable.

Foil shield

Black wire

Drain wire

Clear wire

Insulation

44531

Sink output wiring example

D

DC COM

OUT

+V DC

S

G

+

24V supply

Logic side

User side

Micro800 Sink output

Load

Fuse