Micro830 16-Point Controllers

General – 2080-LC30-16AWB, 2080-LC30-16QWB, 2080-LC30-16QVB

Attribute

2080-LC30-16AWB

2080-LC30-16QWB

2080-LC30-16QVB

Number of I/O

16 (10 inputs, 6 outputs)

Dimensions
HxWxD

90 x 100 x 80 mm
(3.54 x 3.94 x 3.15 in.)

Shipping weight, approx.

0.302 kg (0.666 lb)

Wire size

0.14…2.5 mm

2

(26…14 AWG) solid copper wire or

0.14…1.5 mm

2

(26…14 AWG) stranded copper wire

rated @ 90 °C (194 °F ) insulation max

Wiring category

(1)

2 – on signal ports
2 – on power ports

Wire type

Use Copper Conductors only

Terminal screw torque

0.6 Nm (4.4 lb-in.) max
(using a 2.5 mm (0.10 in.) flat-blade screwdriver)

Input circuit type

120V AC

12/24V sink/source (standard)
24V sink/source (high-speed)

Output circuit type

Relay

12/24V DC sink transistor (standard
and high-speed)

Event input interrupt
support

Yes

Power consumption

7.88 W

Power supply voltage range

20.4…26.4V DC Class 2

I/O rating

Input 120V AC, 16 mA
Output 2 A, 240V AC, general use

Input 24V DC, 8.8 mA
Output 2 A, 240V AC, general use

Input 24V DC, 8.8 mA
Output 24V DC, 1 A per point
(Surrounding air temperature 30 °C)
24V DC, 0.3 A per point (Surrounding
air temperature 65 °C)

Isolation voltage

250V (continuous), Reinforced Insulation Type, Outputs to Aux and Network,
Inputs to Outputs

2080-LC30-16AWB: Type tested for 60 s @ 3250V DC I/O to Aux and Network,
Inputs to Outputs
2080-LC30-16QWB: Type tested for 60 s @ 720V DC, Inputs to Aux and
Network, 3250V DC Outputs to Aux and Network, Inputs to Outputs

50V (continuous), Reinforced
Insulation Type, I/O to Aux and
Network, Inputs to Outputs
Type tested for 60s @ 720 V DC, I/O
to Aux and Network, Inputs to
Outputs

Pilot duty rating

C300, R150

Insulation stripping length

7 mm (0.28 in.)

Enclosure type rating

Meets IP20

North American temp code

T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

.