Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Chapter 5 Communication Connections

Ethernet Host Name

Micro800 controllers implement unique host names for each controller, to be
used to identify the controller on the network. The default host name is
comprised of two parts: product type and MAC address, separated by a hyphen.
For example: 2080LC50-xxxxxxxxxxxx, where xxxxxxxxxxxx is the MAC
address.

The user can change the host name using the CIP Service Set Attribute Single
when the controller is in Program/Remote Program mode.

Configure CIP Serial Driver

1.

Open your Connected Components Workbench project. On the device
configuration tree, go to the Controller properties. Click Serial port.

2.

Select CIP Serial from the Driver field.

3.

Specify a baud rate. Select a communication rate that all devices in your
system support. Configure all devices in the system for the same
communication rate. Default baud rate is set @ 38400 bps.

4.

In most cases, parity and station address should be left at default settings.

5.

Click Advanced Settings and set Advanced parameters.