Configure ascii – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 64

Advertising
background image

50

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Chapter 5 Communication Connections

3.

Specify the following parameters:
• Baud rate
• Parity
• Unit address
• Modbus Role (Master, Slave, Auto)

4.

Click Advanced Settings to set advanced parameters.
Refer to the table for available options and default configuration for
advanced parameters.

Configure ASCII

1.

Open your Connected Components Workbench project. On the device
configuration tree, go to Controller properties. Click Serial Port.

Modbus RTU Parameters

Parameter

Options

Default

Baud Rate

1200, 2400, 4800, 9600, 19200, 38400

19200

Parity

None, Odd, Even

None

Modbus Role

Master, Slave, Auto

Master

Modbus RTU Advanced Parameters

Parameter

Options

Default

Media

RS-232, RS-232 RTS/CTS, RS-485

RS-232

Data bits

Always 8

8

Stop bits

1, 2

1

Response timer

0…999,999,999 milliseconds

200

Broadcast Pause

0…999,999,999 milliseconds

200

Inter-char timeout

0…999,999,999 microseconds

0

RTS Pre-delay

0…999,999,999 microseconds

0

RTS Post-delay

0…999,999,999 microseconds

0