Input and Output Signals

Multiple input/output control signals are required for each motion axis, as
described in the next tables. PTO Pulse and PTO Direction are required for an
axis. The rest of the input/outputs can be disabled and re-used as regular I/O.

These I/O can be configured through the axis configuration feature in
Connected Components Workbench. Any outputs assigned for motion should
not be controlled in the user program.

See

Motion Axis Configuration in Connected Components Workbench on

page 89

.

Fixed PTO Input/Output

Motion Signals

PTO0 (EM_00)

PTO1 (EM_01)

PTO2 (EM_02)

Logical Name
in Software

Name on
Terminal
Block

Logical Name
in Software

Name on
Terminal
Block

Logical Name in
Software

Name on
Terminal Block

PTO pulse

_IO_EM_DO_00

O-00

_IO_EM_DO_01

O-01

IO_EM_DO_02

O-02

PTO direction

_IO_EM_DO_03

O-03

_IO_EM_DO_04

O-04

IO_EM_DO_05

O-05

Lower (Negative) Limit switch

_IO_EM_DI_00

I-00

_IO_EM_DI_04

I-04

IO_EM_DI_08

I-08

Upper (Positive) Limit switch

_IO_EM_DI_01

I-01

_IO_EM_DI_05

I-05

IO_EM_DI_09

I-09

Absolute Home switch

_IO_EM_DI_02

I-02

_IO_EM_DI_06

I-06

IO_EM_DI_10

I-10

Touch Probe Input switch

_IO_EM_DI_03

I-03

_IO_EM_DI_07

I-07

IO_EM_DI_11

I-11

Configurable input/output

Motion Signals

Input/Output

Notes

Servo/Drive On

OUTPUT

Can be configured as any embedded output.

Servo/Drive Ready

INPUT

Can be configured as any embedded input.

In-Position signal (from
Servo/motor)

INPUT

Can be configured as any embedded input.

Home Marker

INPUT

Can be configured as any embedded input, from input
0...15.

IMPORTANT

If an output is configured for motion, then that output can no longer be
controlled or monitored by the user program and cannot be forced. For
example, when a PTO Pulse output is generating pulses, the
corresponding logical variable IO_EM_DO_xx will not toggle its value
and will not display the pulses in the Variable Monitor but the physical
LED will give an indication.

If an input is configured for motion, then forcing the input only affects the
user program logic and not motion. For example, if the input Drive Ready
is false, then the user cannot force Drive Ready to true by forcing the
corresponding logical variable IO_EM_DI_xx to be true.