Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 264

Advertising
background image

248

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Appendix G System Loading

Calculate External AC Power Supply Loading for your Micro830 Controller

To calculate External AC Power Supply Loading:

• Get total sensor current loading. For this example, assume it is 250 mA.
• Calculate Total Power Loading by Sensor using this formula:

(24V * 250 mA) 6 W.

• Derive External AC Power Supply Loading using this formula:

AC Power Supply Loading

= Total Power calculated for a Micro800

system with Plug in + Total power loading by Sensor

As an example, a 48-point Micro850 controller with2 plug-ins, and 2085-IQ16
and 2085-IF4 expansion I/O, and 250mA sensor current (6W sensor power) will
have the following Total Loading for AC Power Supply:

Total loading for AC power supply

= 17.87W + 6W = 23.87 W

ATTENTION: Maximum loading to AC Power Supply is limited to 38.4 W
with maximum surrounding ambient temperature limited to 65 °C.

Advertising
This manual is related to the following products: