Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

29

Chapter

4

Wire Your Controller

This chapter provides information on the Micro830 and Micro850 controller
wiring requirements. It includes the following sections:

Wiring Requirements and
Recommendation

• Allow for at least 50 mm (2 in.) between I/O wiring ducts or terminal

strips and the controller.

Topic

Page

Wiring Requirements and Recommendation

29

Use Surge Suppressors

30

Recommended Surge Suppressors

32

Grounding the Controller

33

Wiring Diagrams

33

Controller I/O Wiring

36

Minimize Electrical Noise

37

Analog Channel Wiring Guidelines

37

Minimize Electrical Noise on Analog Channels

37

Grounding Your Analog Cable

38

Wiring Examples

38

Embedded Serial Port Wiring

39

WARNING: Before you install and wire any device, disconnect power to
the controller system.

WARNING: Calculate the maximum possible current in each power and
common wire. Observe all electrical codes dictating the maximum
current allowable for each wire size. Current above the maximum ratings
may cause wiring to overheat, which can cause damage.
United States Only: If the controller is installed within a potentially
hazardous environment, all wiring must comply with the requirements
stated in the National Electrical Code 501-10 (b).