This chapter covers some common tasks and quickstart instructions that are
aimed to make you familiar with the in Connected Component Workbench. The
following quickstarts are included:

Flash Upgrade Your
Micro800 Firmware

This quick start will show you how to flash update the firmware in a Micro800
controller using ControlFLASH. ControlFLASH is installed or updated with
the latest Micro800 firmware when Connected Components Workbench
software is installed on your computer.

On Micro850 controllers, users can use flash upgrade their controllers through
the Ethernet port, in addition to the USB.

1. Through USB

: Verify successful RSLinx Classic communications with

your Micro800 controller by USB using RSWho. Micro810 12-pt.
controller uses the 12PtM810_xxxxx driver and the Micro830/Micro850
uses the AB_VBP-x driver.

Topic

Page

Flash Upgrade Your Micro800 Firmware

181

Establish Communications Between RSLinx and a Micro830/Micro850
Controller through USB

186

Configure Controller Password

192

Use the High Speed Counter

196

Forcing I/Os

209

ATTENTION: All Ethernet settings are reverted to factory default after
a ControlFlash firmware upgrade. For users who need to use the same
static IP address as previously set, for example, use the Memory
Module to store project settings prior to a flash upgrade so that you
can have the option to restore your original Ethernet settings.