Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

73

Motion Control with PTO and PWM Chapter 7

Simultaneous Execution of Two Movement Function Blocks
(Busy Output = True)

The general rule is that when a movement function block is busy, then a function
block with the same instance (for example, MC_MoveRelative2) cannot be
executed again until the function block status is not busy.

When a movement function block is busy, a function block with a different
instance

(for example, MC_MoveRelative1 and MC_MoveAbsolute1 on the

same axis) can abort the currently executing function block. This is mostly useful
for on-the-fly adjustments to position, velocity, or to halt after a specific distance.

Example: Move to Position Ignored Due to Busy

TIP

MC_MoveRelative, MC_MoveAbsolute will be busy until final position is
reached. MC_MoveVelocity, MC_Halt, and MC_Stop will be busy until
final velocity is reached.

V

elocit

y

Time

Execute1

Busy1

46054

V

elocit

y

Time

Execute1

Busy1

This command is ignored

Simple move position using one
instance of MC_MoveRelative,
MC_MoveAbsolute

For simple moves, the
movement function block
finishes. Busy output indicates
that the function block is
executing and must be allowed
to finish before Execute input is
toggled again.

If Execute is toggled again
before Busy is false, the new
command is ignored. No error is
generated.

46053