Use the High-Speed Counter and Programmable Limit Switch Chapter 8

At that point, the next presets (HSCHP and HSCLP) defined in the PLS data
become active.

When the HSC counts to that new preset, the new output data is written
through the HSC mask. This process continues until the last element within the
PLS data block is loaded. At that point the active element within the PLS data
block is reset to zero. This behavior is referred to as circular operation.

If invalid data is loaded during operation, an HSC error is generated and causes a
controller fault.

You can use the PLS in Up (high), Down (low), or both directions. If your
application only counts in one direction, ignore the other parameters.

The PLS function can operate with all of the other HSC capabilities. The ability
to select which HSC events generate a user interrupt are not limited.

PLS Example

Setting Up the PLS data

Using Connected Components Workbench, define the PLS data HSC_PLS’s
dimension as [1..4].

TIP

The HSCHPOutput is only written when HSCHP is reached. The
HSCLPOutput is written when HSCLP is reached.

TIP

Output High Data is only operational when the counter is counting up.
Output Low Data is only operational when the counter is counting
down.

PLS Data Definition

Data

Description

Data Format

HSCHP

High Preset

32-bit signed integer

HSCLP

Low Preset

HSCHPOutput

Output High Data

32-bit binary
(bit 31--> 0000 0000 0000 0000 0000 0000 0000
0000 <--bit 0)

HSCLPOutput

Output Low Data