How to autotune – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 257

Advertising
background image

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

241

IPID Function Block Appendix F

How to Autotune

Before you autotune, you need to:

• Verify that your system is constant when there is no control. For example,

for temperature control, process value should remain at room temperature
when there is no control output.

• Configure the set point to 0.
• Set Auto Input to False.
• Set the Gain parameter as follows:

Step

REAL

Step value for AutoTune. Must be greater than noise band and less
than ½ load.

ATDynamSet

REAL

Auto Tune time. Set the time to wait for stabilization after the step
test (in seconds). Auto Tune process will be stopped when
ATDynamSet time expires.

ATReset

BOOL

Determines whether the output value is reset to zero after an
AutoTune sequence:

True – Reset IPIDCONTROLLER output to zero after Auto tune

process.

False – leaves output at load value

(1) The application engineer can estimate the value of ATParams.Deviation by observing the value of Proces input.

For example, in a project that involves the control of temperature, if the temperature stabilizes around 22 °C,
and a fluctuation of 21.7…22.5 °C is observed, the value of ATParams.Deviation will be (22.5-21.7)/2=0.4.

AT_Param Data Type

Parameter

Type

Description

GAIN Parameter Values

GAIN Parameter

Value

DirectActing

According to operation:
TRUE (for example, Cooling), or
FALSE (for example, Heating)

DerivativeGain

Typically set to 0.1 or 0.0

ProportionalGain

0.0001

TimeIntegral

0.0001

TimeDerivative

0.0