Chapter 5 Communication Connections

Modbus RTU

Modbus is a half-duplex, master-slave communications protocol. The Modbus
network master reads and writes bits and registers. Modbus protocol allows a
single master to communicate with a maximum of 247 slave devices. Micro800
controllers support Modbus RTU Master and Modbus RTU Slave protocol. For
more information on configuring your Micro800 controller for Modbus
protocol, refer to the Connected Components Workbench Online Help. For
more information about the Modbus protocol, refer to the Modbus Protocol
Specifications (available from

http://www.modbus.org

).

See

Modbus Mapping for Micro800 on page 175

for information on Modbus

mapping. To configure the Serial port as Modbus RTU, see

Configure Modbus

RTU on page 49

.

Modbus/TCP Client/Server

The Modbus/TCP Client/Server communication protocol uses the same
Modbus mapping features as Modbus RTU, but instead of the Serial port, it is
supported over Ethernet. Modbus/TCP Server takes on Modbus Slave features
on Ethernet.

The Micro850 controller supports up to 16 simultaneous Modbus TCP Client
connections and 16 simultaneous Modbus TCP Server connections.

No protocol configuration is required other than configuring the Modbus
mapping table. For information on Modbus mapping, see

Modbus Mapping for

Micro800 on page 175

.

CIP Symbolic Client/Server

CIP Symbolic is supported by any CIP compliant interface including Ethernet
(EtherNet/IP) and Serial Port (CIP Serial). This protocol allows HMIs to easily
connect to the Micro830/Micro850 controller.

Micro850 controllers support up to 16 simultaneous EtherNet/IP Client
connections and 16 simultaneous EtherNet/IP Server connections.

CIP Serial, supported on both Micro830 and Micro850 controllers, makes use of
DF1 Full Duplex protocol, which provides point-to-point connection between
two devices.

TIP

Use MSG_MODBUS instruction to send Modbus messages over
serial port.

TIP

Use MSG_MODBUS2 instruction to send Modbus TCP message over
Ethernet port.